11.3.5 Mains filter selection
TT/TN system
1)
Rated temperature = 50° C
IT system
NOTE!
The rated current of the filters that are used must be larger than or have same RMS-
value as the actual power suppl.y current (actual power supply current = RMS-value
of the power supply current during the entire cycle time of the drive). During short-
time operation (S3), the RMS-value is calculated as follows:
I
rms
1
T
---
i
2
0
T
dt
=
I
rated AC
1)
Type
Part No.
7 A BFN-3-1 - 0007 - 001
314277
16 A BFN-3-1 - 0016 - 001
314278
30 A BFN-3-1 - 0030 - 001
314279
42 A BFN-3-1 - 0042 - 001
314280
56 A BFN-3-1 - 0056 - 001
314281
75 A BFN-3-1 - 0075 - 001
314282
100 A BFN-3-1 - 0100 - 001
314283
130 A BFN-3-1 - 0130 - 001
314284
150 A
EPCOS B84143A0150R410
437618
180 A BFN-3-1 - 0180 - 001
314285
250 A BFN-3-1 - 0250 - 001
373891
320 A BFN-3-1 - 0320 - 001
439384
BFN-3-1 - 0320 - 101
373896
400 A BFN-3-1 - 0400 - 101
373900
600 A BFN-3-1 - 0600 - 001
373901
BFN-3-1 - 0600 - 101
419997
1000 A BFN-3-1 - 1000 - 101
423683
NOTE!
EMC limit values are not defined for transient emission in power systems without
grounded star point (IT system). A fault state (motor ground fault) can lead to the
damage of the mains filter.
It is not recommended to use mains filter in IT systems. The transient emission can
exceed the limit values of category C3.