Fieldbus communication
Instruction handbook
b maXX
BM5500, BM5600, BM5700
Document No.: 5.13008.10
Baumüller Nürnberg GmbH
226
8.4
n
Please, observe an EMC-compatible laying of the Ethernet connection cables!
n
The following cables were released for use by Baumüller:
Ethernet connection cable;
Commissioning
.
The following preconditions must be fulfilled before commissioning:
1 BM5500, BM5600, BM5700
with VARAN is installed correctly.
n
Ethernet connection cables are wired correctly.
2
The control cabinet is properly locked and all safety devices are operating.
3
The
b maXX
BM5500, BM5600, BM5700
device is ready-to-use.
4
Create a Lasal-Class2 project using the driver classes for
BM5500, BM5600, BM5700
drives for cyclic and service data communication.
5
Start the VARAN control
Address switch
By means of the address switches S1 to S4 the IP-address is set
(Refer to settings
Setting the IP address with address switches
Parameters
The parameter settings determine the behavior of the VARAN-Slave in operation. Param-
eters are set with the software ProDrive.
1
Start ProDrive
2
Click on „Project Tree“.
3
Communication settings with ProDrive
n
Project Tree: Configuration/Fieldbus Slave
(refer also Parameter manual
b maXX
BM5500, BM5600, BM5700
)
m
Set Synchronization to „On“
m
Set Fieldbus cycle time according VARAN cycle time (1 ms, 2 ms, 4 ms or 8 ms)
m
Source sync signal = „field bus“