Technical Data
Instruction handbook
b maXX
BM5500, BM5600, BM5700
Document No.: 5.13008.10
59
3
3.3.7
Cooling
Cooling air temperature
1)
Min. 0 °C to max. 55 °C (rated temperature: 40 °C)
Cooling air requirement
2)
Refer to
Cooling water temperature
4)
Min. „Cooling air temperature“
1)
to max. 40 °C at Cold Plate devices BM5XXX-CXXX)
Cooling water flow rate
3) 4) 6)
BM553X, BM554X, BM555X, BM556X
Min. 4 l/min. up to max. 15 l/min.
BM563X, BM564X, BM565X, BM566X
BM564X-FXX9, BM565X-FXX9,
BM566X-FXX9
Min. 10 l/min. up to max. 15 l/min
BM5755, BM5766
BM557X, BM577X
Min. 15 l/min. up to max. 25 l/min.
Cooling water pressure
3)
Max. 6 bar
Cooling water hysteresis
Max. 5 K in the static and the dynamic operation
Hot water heating
(cooling water inlet to cooling water outlet)
3)
[K]
<14.35
l/min
kW
------------
K
Power loss kW
Cooling water flow [l/min]
---------------------------------------------------------------------------
Pressure loss at the water cooler
3)
0.5 bar at 10 l/min
Mounting board temperature at Cold Plate
5)
Min. „Cooling air temperature“
1)
to max. 55 °C
(rated temperature: 40 °C)
At water cooling
4)
:
water outlet temperature 40 °C
surface temperature 42 °C
1)
Air temperature in the entire suction area of the device.
2)
The cooling air requirement corresponds at least to that of a free-blowing device. Free-blowing means, that the air inlet and the air outlet
operates unrestricted. With the mounting of the device into a control cabinet it therefore can be necessary to use additional fans, so that
the necessary cooling air requirement is covered. If the necessary cooling air requirement of the power heatsink is not provided, then
the output power of the device has to be reduced.
Figure 32:
Cooling air requirement