7.11.3 Electrical connection power unit
Power system
1U1, 1V1, 1W1, PE
Max. cross-section
of connection
Connection
technology
Torque
Load capacity
not v
alid for
po
we
r mo
dule
s
BM551X
2.5 mm
2
Terminal block
-
Refer to
BM552X
4.0 mm
2
Screw terminal
Min. 0.5 Nm
Max. 0.6 Nm
BM553X
BM563X
25 mm
2
Screw terminal
Min. 2 Nm
Max. 2.3 Nm
BM554X
BM564X
50 mm
2
Screw terminal
Min. 6 Nm
Max. 8 Nm
BM555X
BM565X
BM575X
2 x 95 mm
2 1)3)
Cable lug
for M8
Min. 10 Nm
Max. 13 Nm
BM556X
BM566X
BM576X
2 x 185 mm
2 2)3)
Cable lug
for M10
Min. 12 Nm
Max. 25 Nm
BM557X
BM577X
2 x 185 mm
2 2)
4 x 95 mm
2 1)
Cable lug
for M10
Min. 12 Nm
Max. 25 Nm
1)
The cable lug may be 25 mm wide at most. The maximum cable diameter is dependent on the cable lug. In
case the cable lug, which you use, can safely clamp a stronger cable than 95 mm
2
, you may also use stronger
cables than 95 mm
2
. Also refer to
2)
The cable lug may be 35 mm wide at most. The maximum cable diameter is dependent on the cable lug. In
case the cable lug, which you use, can safely clamp a stronger cable than 185 mm
2
, you may also use stron-
ger cables than 185 mm
2
. Also refer to
3)
One cable of the mentioned cross section is sufficient for the operation.