DC link
1C1 and 1D1
2)
Ballast
Ba+ and Ba-
1)
Max. cross-section
of connection
Connection tech-
nology
Torque
Load capacity
1C1 and 1D1
2)
Ba+ and Ba-
3)
BM551X
2.5 mm
2
Terminal block
-
Refer to
BM552X
4.0 mm
2
Screw terminal
Min. 0.5 Nm
Max. 0.6 Nm
BM553X
BM563X
25 mm
2
Screw terminal
Min. 2 Nm
Max. 2.3 Nm
BM554X
BM564X
50 mm
2
Screw terminal
Min. 6 Nm
Max. 8 Nm
BM555X
BM565X
BM575X
2 x 95 mm
2 4)6)
Cable lug
for M8
Min. 10 Nm
Max. 13 Nm
BM556X
BM566X
BM576X
2 x 185 mm
2 5)6)
Cable lug
for M10
Min. 12 Nm
Max. 25 Nm
BM557X
BM577X
2 x 185 mm
2 5)
Cable lug
for M10
Min. 12 Nm
Max. 25 Nm
Wiring diagrams
Instruction handbook
b maXX
BM5500, BM5600, BM5700
Document No.: 5.13008.10
Baumüller Nürnberg GmbH
190
7.11
1)
Not short-circuit-proof, consider maximum load! Refer to „Brake resistor external“ in chapter
2)
Not short-circuit-proof, consider maximum load! Refer to „Connected load DC link“ in chapter
3)
Refer to „Permitted brake resistor continuous power“ in chapter
4)
The cable lug may be 25 mm wide at most. The maximum cable diameter is dependent on the cable lug. In
case the cable lug, which you use, can safely clamp a stronger cable than 95 mm
2
, you may also use stronger
cables than 95 mm
2
5)
The cable lug may be 35 mm wide at most. The maximum cable diameter is dependent on the cable lug. In
case the cable lug, which you use, can safely clamp a stronger cable than 185 mm
2
, you may also use stron-
ger cables than 185 mm
2
. Also refer to
6)
One cable of the mentioned cross section is sufficient for the operation.