9440300990 Rev J
45
DECS-250
Protection
Figure 30. Loss of Sensing Protection Settings
A
Voltage Balanced Level:
Adjustable from 0 to 100% in 0.1% increments.
B
Voltage Unbalanced Level:
Adjustable from 0 to 100% in 0.1% increments.
C
Time Delay:
Adjustable from 0 to 30 seconds in 0.1 second increments.
D
Transfer to Manual:
Select Disabled or Enabled.
E
Mode:
Select Disabled or Enabled.
Frequency Protection
BESTCOMSPlus Navigation Path:
Settings Explorer, Protection, Frequency
HMI Navigation Path:
Settings, Protection, Frequency Protection 81
The frequency of the generator terminal voltage is monitored for overfrequency and under-frequency
conditions.
Overfrequ
e
ncy
An overfrequency condition occurs when the frequency of the generator voltage exceeds the 81O pickup
threshold
A
for the duration of the 81O time delay setting
B
. Overfrequency protection can be enabled and
disabled
C
without altering the pickup and time delay settings. Overfrequency pickup and trip elements in
BESTlogic
Plus
can be used in a logic scheme to initiate corrective action in response to the condition.
BESTCOMS
Plus
overfrequency settings are illustrated in Figure 31.
Figure 31. Overfrequency Protection Settings
A
Overfrequency (81O) Pickup (Hz)
: Adjustable from 30 to 70 hertz in 0.01 hertz increments.
B
Overfrequency (81O) Time Delay (s)
: Adjustable from 0.1 to 300 seconds in 0.1 second increments.
C
Overfrequency (81O) Mode
: Select Disabled or Over.
Содержание DECS-250
Страница 2: ......
Страница 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Страница 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Страница 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Страница 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Страница 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Страница 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Страница 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Страница 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Страница 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Страница 108: ...92 9440300990 Rev J Power System Stabilizer DECS 250 Figure 85 PSS Function Blocks and Software Switches ...
Страница 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Страница 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Страница 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Страница 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Страница 128: ...112 9440300990 Rev J Mounting DECS 250 Figure 105 Panel Cutting and Drilling Dimensions for DECS 250 Panel Mounting ...
Страница 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Страница 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Страница 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Страница 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Страница 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Страница 341: ...9440300990 Rev J 325 DECS 250 Contact Expansion Module Figure 188 CEM 2020 Input Contact and Output Contact Terminals ...
Страница 351: ......