9440300990 Rev J
293
DECS-250
Specifications
Relay Output 9 ........................... RLY 9, RLY 9
Relay Output 10 ......................... RLY 10, RLY 10
Relay Output 11 ......................... RLY 11, RLY 11
Field Power Output
Continuous Rating ............................ 15 Adc
Terminals.......................................... F+, F–
Minimum 10-Second Forcing Output Rating
60 Vac Input ..................................... 50 Vdc, 30 Adc
120 Vac Input ................................... 100 Vdc, 30 Adc
240 Vac Input ................................... 200 Vdc, 30 Adc
Minimum Field Resistance
32 Vdc Application ........................... 2.13
Ω
63 Vdc Application ........................... 4.20
Ω
125 Vdc Application ......................... 8.33
Ω
Regulation
FCR Operating Mode
Setpoint Range ................................ 0 to 18 Adc, in increments of 0.1%
Regulation Accuracy ........................ ±1.0% of the nominal value for 10% of the power input voltage
change or 20% of the field resistance change. Otherwise, ±5.0%
FVR Operating Mode
Setpoint Range ................................ 0 to 270 Vdc, in increments of 0.1%
Regulation Accuracy ........................ ±1.0% of the nominal value for 10% of the power input voltage
change or 20% of the field resistance change. Otherwise, ±5.0%
AVR Operating Mode
Setpoint Range ................................ 70 to 120% of rated generator voltage, in increments of 0.1%
Regulation Accuracy ........................ ±0.25% over load range at rated PF with constant generator
frequency and ambient temperature
Steady-State Stability ....................... ±0.25% at rated PF with constant generator frequency and ambient
temperature
Temperature Drift ............................. ±0.5% between 0 and 40
°
C at constant load and generator
frequency
Var Operating Mode
Setpoint Range ................................ –100% (leading) to +100% (lagging) of the generator nominal
apparent power in increments of 0.1%
Regulation Accuracy ........................ ±2.0% of the nominal generator apparent power rating at the rated
generator frequency
Power Factor Operating Mode
Setpoint Range ................................ 0.5 to 1.0 (lagging) and –0.5 to -1.0 (leading), in increments of 0.005
Regulation Accuracy ........................ ±0.02 PF of the PF setpoint for the real power between 10 and 100%
at the rated frequency
Содержание DECS-250
Страница 2: ......
Страница 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Страница 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Страница 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Страница 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Страница 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Страница 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Страница 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Страница 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Страница 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Страница 108: ...92 9440300990 Rev J Power System Stabilizer DECS 250 Figure 85 PSS Function Blocks and Software Switches ...
Страница 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Страница 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Страница 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Страница 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Страница 128: ...112 9440300990 Rev J Mounting DECS 250 Figure 105 Panel Cutting and Drilling Dimensions for DECS 250 Panel Mounting ...
Страница 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Страница 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Страница 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Страница 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Страница 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Страница 341: ...9440300990 Rev J 325 DECS 250 Contact Expansion Module Figure 188 CEM 2020 Input Contact and Output Contact Terminals ...
Страница 351: ......