Event Recorder
DECS-250
Setup
When oscillography is enabled
A
, each record can consist of up to six user-selectable parameters
B
with up
to 1,200 data points recorded for each parameter. Data log setup settings are illustrated in Figure 80.
A pre-trigger-points setting
C
enables a user-defined number of data points recorded prior to the event
trigger to be included in a data log. The value of this setting affects the duration
D
of the recorded pre-
trigger points, the recorded post-trigger points
E
, and the duration of the post-trigger points
F
. A sample
interval setting
G
establishes the sample rate of the data points recorded. The value of this setting affects
the pre- and post-trigger duration values and the total recording duration
H
for a data log.
Figure 80. Data Log Setup
A
Enable:
Select Enabled or Disabled.
B
Log Parameters:
For each of the six parameters, select No Level Trigger, Vab, Vbc, Vca, Vbus, Ia, Ib, Ic,
Vavg, Iavg, Iaux, Vfd, Ifd, Vaux, kW, kvar, kVA, PF, V1, V2, I1, I2, G Hz, B Hz, Test, Ptest, TermF,
CompF, PsskW, Vtmag, x2, WashW, x5, WashP, x7, x8, x9, x10, x11, MechP, Synth, Tfltl, x29, x15, x16,
x17, x31, Prelim, Post, POut, CntOp, TrnOp, ErrIn, Oel Output, Uel Output, Scl Output, varLimOutput,
Null Balance, PositionInd, AvrOut, FcrErr, FcrState, FcrOut, FvrErr, FvrState, FvrOut, var/PfErr,
var/PfState, var/PfOut, Oel State, Uel State, Scl State, VarLimState, Droop, Network Load Share, Oel
Ref, Uel Ref, Scl Ref, Scl PfRef, VarLimRef, ProgrammableDiagnostic1, ProgrammableDiagnostic2,
ProgrammableDiagnostic3, ProgrammableDiagnostic4, ProgrammableDiagnostic5,
ProgrammableDiagnostic6. (Selecting “No Level Trigger” excludes a parameter from data logging.)
C
Pre-Trigger Points:
Adjustable from 0 to 1,199 in increments of 1.
D
Pre-Trigger Duration:
Read-only value based on the Pre-Trigger Points and Sample Interval settings.
E
Post-Trigger Points:
Read-only value based on the Pre-Trigger Points setting.
F
Post-Trigger Duration:
Read-only value based on the Pre-Trigger Points and Sample Interval settings.
G
Sample Interval:
Adjustable from 4 to 10,000 milliseconds in 4 millisecond increments for 60 Hz nominal
generator frequency. Adjustable from 5 to 12,500 milliseconds in 5 millisecond increments for 50 Hz
nominal generator frequency.
H
Total Duration:
Read-only value is the sum of the pre- and post-trigger duration values.
Triggers
BESTCOMSPlus Navigation Path:
Settings Explorer, Report Configuration, DataLog
HMI Navigation Path:
Settings, Configuration Settings, Data Log
Data logging may be triggered by mode triggers, logic triggers, level triggers, or manually through
BESTCOMS
Plus
.
Содержание DECS-250
Страница 2: ......
Страница 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Страница 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Страница 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Страница 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Страница 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Страница 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Страница 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Страница 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Страница 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Страница 108: ...92 9440300990 Rev J Power System Stabilizer DECS 250 Figure 85 PSS Function Blocks and Software Switches ...
Страница 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Страница 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Страница 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Страница 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Страница 128: ...112 9440300990 Rev J Mounting DECS 250 Figure 105 Panel Cutting and Drilling Dimensions for DECS 250 Panel Mounting ...
Страница 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Страница 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Страница 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Страница 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Страница 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Страница 341: ...9440300990 Rev J 325 DECS 250 Contact Expansion Module Figure 188 CEM 2020 Input Contact and Output Contact Terminals ...
Страница 351: ......