9440300990 Rev J
21
DECS-250
Synchronizer
A failed generator is recognized when the generator voltage or frequency does not meet the established
generator stability criteria for the duration of the failed generator activation delay
C
. Generator stability
parameters are described in
Generator Stability
.
Generator Stability
Before initiating a breaker closure (tying the generator to a stable or dead bus), the generator voltage
must be stable. Several settings are used to determine generator stability. These settings include pickup
and dropout levels for overvoltage
D
, undervoltage
E
, overfrequency
F
, and under-frequency
G
. Recognition of
generator stability is further controlled by a generator stability activation delay
H
. Breaker closure is not
considered if the voltage conditions are not within the stability pickup and dropout settings for the duration
of the stability activation delay.
Bus Condition
A dead bus is recognized by the DECS-250 when the bus voltage decreases below the dead bus
threshold
I
for the duration of the dead bus activation delay
J
.
A failed bus is recognized when the bus voltage or frequency does not meet the established stability
criteria for the duration of the failed bus activation delay
K
. Bus stability parameters are described in
Bus
Stability
.
Bus Stability
Before initiating a breaker closure (tying the generator to a live bus), the bus voltage must be stable.
Several settings are used to determine bus stability. These settings include pickup and dropout levels for
overvoltage
L
, undervoltage
M
, overfrequency
N
, and underfrequency
O
. Recognition of bus stability is further
controlled by a bus stability activation delay
P
. Breaker closure is not considered if the voltage conditions
are not within the stability pickup and dropout settings for the duration of the stability activation delay.
Содержание DECS-250
Страница 2: ......
Страница 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Страница 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Страница 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Страница 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Страница 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Страница 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Страница 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Страница 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Страница 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Страница 108: ...92 9440300990 Rev J Power System Stabilizer DECS 250 Figure 85 PSS Function Blocks and Software Switches ...
Страница 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Страница 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Страница 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Страница 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Страница 128: ...112 9440300990 Rev J Mounting DECS 250 Figure 105 Panel Cutting and Drilling Dimensions for DECS 250 Panel Mounting ...
Страница 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Страница 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Страница 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Страница 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Страница 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Страница 341: ...9440300990 Rev J 325 DECS 250 Contact Expansion Module Figure 188 CEM 2020 Input Contact and Output Contact Terminals ...
Страница 351: ......