26
9440300990 Rev J
Regulation
DECS-250
•
The BESTCOMS
Plus
Control Panel screen (available in the BESTCOMS
Plus
Metering Explorer)
•
A raise or lower command transmitted through the DECS-250 Modbus port
The range of adjustment is defined by Minimum
J
and Maximum
K
settings that are expressed as a
percentage of the rated field voltage. The length of time required to adjust the FVR setpoint from one limit
to the other is controlled by a Traverse Rate
L
setting. These settings are illustrated in Figure 15.
Figure 15. AVR, FCR, and FVR Regulation Settings
A
AVR Setpoint
: Range of adjustment is based on the rated generator voltage and limited by the AVR Min
(B) and Max (C) settings.
B
Min (% of rated)
: Adjustable from 70 to 120% in 0.1% increments.
C
Max (% of rated)
: Adjustable from 71 to 120% in 0.1% increments.
D
Traverse Rate (s)
: Adjustable from 10 to 200 seconds in 1 second increments.
E
FCR Setpoint
: Range of adjustment is based on the rated field current and limited by the FCR Min (F)
and Max (G) settings.
F
Min (% of rated)
: Adjustable from 0 to 120% in 0.1% increments.
G
Max (% of rated)
: Adjustable from 0 to 120% in 0.1% increments.
H
Traverse Rate (s)
: Adjustable from 10 to 200 seconds in 1 second increments.
I
FVR Setpoint
: Range of adjustment is based on the rated field voltage and limited by the FCR Min (J)
and Max (K) settings.
J
Min (% of rated)
: Adjustable from 0 to 150% in 0.1% increments.
K
Max (% of rated)
: Adjustable from 0 to 150% in 0.1% increments.
L
Traverse Rate:
Adjustable from 10 to 200 seconds in 1 second increments.
Var
When operating in var mode, the DECS-250 regulates the reactive power (var) output of the generator
based on the var setpoint
A
. The setting range of the var setpoint depends on the generator ratings and
other associated settings. Var setpoint adjustment is made through:
•
Application of contacts at DECS-250 contact inputs configured for raising and lowering the active
setpoint
•
Application of an analog control signal at the DECS-250 Auxiliary Control input
•
The BESTCOMS
Plus
Control Panel screen (available in the BESTCOMS
Plus
Metering Explorer)
•
A raise or lower command transmitted through the DECS-250 Modbus port
The range of adjustment is defined by Minimum
B
and Maximum
C
settings that are expressed as a
percentage of the generator rated kVA output. The length of time required to adjust the Var setpoint from
one limit to the other is controlled by a Traverse Rate setting
D
. A Fine Voltage Adjustment Band setting
E
defines the upper and lower boundaries of voltage correction when operating in var or power factor
regulation modes. Var mode settings are illustrated in Figure 16.
Power Factor
When operating in Power Factor (PF) mode, the DECS-250 controls the var output of the generator to
maintain the Power Factor setpoint
F
as the kW load on the generator varies. The setting range of the PF
Содержание DECS-250
Страница 2: ......
Страница 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Страница 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Страница 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Страница 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Страница 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Страница 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Страница 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Страница 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Страница 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Страница 108: ...92 9440300990 Rev J Power System Stabilizer DECS 250 Figure 85 PSS Function Blocks and Software Switches ...
Страница 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Страница 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Страница 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Страница 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Страница 128: ...112 9440300990 Rev J Mounting DECS 250 Figure 105 Panel Cutting and Drilling Dimensions for DECS 250 Panel Mounting ...
Страница 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Страница 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Страница 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Страница 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Страница 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Страница 341: ...9440300990 Rev J 325 DECS 250 Contact Expansion Module Figure 188 CEM 2020 Input Contact and Output Contact Terminals ...
Страница 351: ......