Communication
DECS-250
One CAN (controller area network) interface (CAN 1) facilitates communication between the DECS-250
and optional modules such as the contact expansion module (CEM-2020) and analog expansion module
(AEM-2020).
A second CAN interface (CAN 2) enables the DECS-250 to provide generator and system parameters to
a generator controller such as the Basler DGC-2020. CAN 2 also permits DECS-250 setpoint and mode
control from an external device connected to the CAN.
Both CAN bus interfaces utilize the SAE J1939 messaging protocol.
DECS-250 CAN parameters are listed and defined in the
CAN Communication
chapter of this manual.
Connections
DECS-250 CAN connections should be made with twisted-pair, shielded cable. Each CAN port
(designated CAN 1 and CAN 2) has a CAN high (H) terminal, a CAN low (L) terminal, and a CAN drain
(SH) terminal. CAN port terminals are illustrated in the
Terminals and Connectors
chapter of this manual.
Port Configuration
Each DECS-250 CAN port must be identified by a unique address number
A
. The baud rate
B
of each port
can be configured for 125 kbps or 250 kbps. Port configuration settings are illustrated in Figure 140.
Figure 140. CAN Port Configuration Settings
A
CAN bus Address:
Adjustable from 1 to 253.
B
Baud Rate:
Select 125 kbps or 250 kbps.
Remote Module Setup
BESTCOMSPlus Navigation Path:
Settings Explorer, Communications, CAN Bus, Remote Module
Setup
HMI Navigation Path:
Settings, Communications, CAN Bus, Remote Module Setup
Optional, external modules, such as the contact expansion module (CEM-2020) and analog expansion
module (AEM-2020), communicate via the DECS-250 CAN 1 interface and are configured through the
DECS-250 BESTCOMS
Plus
interface. These settings are illustrated in Figure 141.
Contact Expansion Module
When enabled
A
for operation, the CEM-2020 CAN address
B
is assigned a unique number and the number
of outputs
C
is selected. Standard module (CEM-2020) provides 24 output contacts and high-current
module (CEM-2020H) provides 18 output contacts.
Analog Expansion Module
When enabled
D
for operation, the AEM-2020 CAN address
E
is assigned a unique address for
communication on the network.
Содержание DECS-250
Страница 2: ......
Страница 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Страница 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Страница 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Страница 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Страница 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Страница 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Страница 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Страница 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Страница 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Страница 108: ...92 9440300990 Rev J Power System Stabilizer DECS 250 Figure 85 PSS Function Blocks and Software Switches ...
Страница 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Страница 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Страница 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Страница 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Страница 128: ...112 9440300990 Rev J Mounting DECS 250 Figure 105 Panel Cutting and Drilling Dimensions for DECS 250 Panel Mounting ...
Страница 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Страница 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Страница 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Страница 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Страница 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Страница 341: ...9440300990 Rev J 325 DECS 250 Contact Expansion Module Figure 188 CEM 2020 Input Contact and Output Contact Terminals ...
Страница 351: ......