312
9440300990 Rev J
Analog Expansion Module
DECS-250
damaged RTD input wire. When enabled, Stop Mode Inhibit
E
turns off RTD input protection when
excitation is stopped.
Each RTD input can be independently configured for over or under mode
F
to annunciate an alarm when
the RTD input signal falls beyond the threshold
G
. Alarms are configured on the
Alarm Configuration,
Alarms
screen in BESTCOMS
Plus
. A user-adjustable activation delay
H
setting delays alarm annunciation
after the threshold has been exceeded.
The remote RTD inputs are incorporated into a BESTlogic
Plus
programmable logic scheme by selecting
them from the
I/O
group in BESTlogic
Plus
. For more details, refer to the
BESTlogicPlus
chapter.
BESTCOMS
Plus
®
settings for remote RTD inputs are illustrated in Figure 177. Remote RTD Input #1 is
shown.
Figure 177. Remote RTD Input Settings
A
Label Text:
An alphanumeric character string with a maximum of 64 characters.
B
Hysteresis:
Adjustable from 0 to 100% in 0.1% increments.
C
RTD Type:
100 Ohm Platinum or 10 Ohm Copper.
D
Arming Delay:
Adjustable from 0 to 300 s in 1 s increments.
E
Stop Mode Inhibit:
Yes or No.
F
Mode:
Disabled, Over, or Under.
G
Threshold:
–
58 to +482
°
F in 1
°
F increments.
H
Activation Delay:
Adjustable from 0 to 300 s in 1 s increments.
Thermocouple Inputs
BESTCOMSPlus Navigation Path:
Settings, Programmable Inputs, Remote Thermocouple Inputs
HMI Navigation Path:
Settings, Programmable Inputs, Remote Thermocouple Inputs
The AEM-2020 provides two thermocouple inputs. The thermocouple inputs are always monitored and
their status is displayed on the appropriate metering screens. To make identifying the thermocouple
inputs easier, a user-assigned name
A
can be given to each input.
Select the amount of hysteresis
B
needed to prevent rapid switching of the alarm. A user-adjustable arming
delay
C
allows configuration of the thermocouple input threshold monitoring in one of two ways. (1) When
the arming delay is set to zero, threshold monitoring is performed all the time, whether or not excitation is
enabled. (2) When the arming delay is set to a non-zero value, threshold monitoring begins when the
arming delay time has expired after system startup is complete. An out-of-range alarm, configured on the
Alarm Configuration, Alarms
screen in BESTCOMS
Plus
, alerts the user of an open or damaged
thermocouple input wire. When enabled, Stop Mode Inhibit
D
turns off thermocouple input protection when
excitation is stopped.
Содержание DECS-250
Страница 2: ......
Страница 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Страница 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Страница 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Страница 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Страница 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Страница 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Страница 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Страница 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Страница 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Страница 108: ...92 9440300990 Rev J Power System Stabilizer DECS 250 Figure 85 PSS Function Blocks and Software Switches ...
Страница 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Страница 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Страница 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Страница 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Страница 128: ...112 9440300990 Rev J Mounting DECS 250 Figure 105 Panel Cutting and Drilling Dimensions for DECS 250 Panel Mounting ...
Страница 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Страница 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Страница 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Страница 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Страница 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Страница 341: ...9440300990 Rev J 325 DECS 250 Contact Expansion Module Figure 188 CEM 2020 Input Contact and Output Contact Terminals ...
Страница 351: ......