9440300990 Rev J
27
DECS-250
Regulation
setpoint is determined by the PF – Leading
G
and PF – Lagging
H
settings. The length of time required to
adjust the PF setpoint from one limit to the other is controlled by a Traverse Rate setting
I
. A Fine Voltage
Adjustment Band setting
E
defines the upper and lower boundaries of voltage correction when the DECS-
250 is operating in Var or Power Factor regulation modes. PF Active Power Level
J
establishes the level of
generator output power (kW) where the DECS-250 switches to/from Droop Compensation/Power Factor
mode. If the level of power decreases below the setting, the DECS-250 switches from Power Factor mode
to Droop Compensation mode. Conversely, as the level of power increases above the setting, the DECS-
250 switches from Droop Compensation mode to Power Factor mode. A setting of 0 to 30% may be
entered in 0.1% increments.
Power Factor mode settings are illustrated in Figure 16.
Figure 16. Var and Power Factor Regulation Settings
A
Setpoint
: Range of adjustment is based on the generator ratings and limited by the Var Minimum (B) and
Var Maximum (C) settings.
B
Min (% of rated)
: Adjustable from –100 to 100% in 0.1% increments.
C
Max (% of rated)
: Adjustable from 0 to 100% in 0.1% increments.
D
Traverse Rate (s)
: Adjustable from 10 to 200 seconds in 1 second increments.
E
Fine Voltage Adjustment Band
: Adjustable from 0 to 30% in 0.01% increments.
F
PF Setpoint
: Range of adjustment is determined by the PF Leading (G) and Lagging (H) settings.
G
PF – Leading
: Adjustable from –1 to –0.5 in 0.005 increments.
H
PF – Lagging
: Adjustable from 0.5 to 1 in 0.005 increments.
I
Traverse Rate (s)
: Adjustable from 10 to 200 seconds in 1 second increments.
J
PF Active Power Level:
Adjustable from 0 to 30% in 0.1% increments.
Pre-Position Setpoints
Each regulation mode has three pre-position setpoints which allow the DECS-250 to be configured for
multiple system and application needs. Each pre-position setpoint can be assigned to a programmable
contact input. When the appropriate contact input is closed, the setpoint is driven to the corresponding
pre-position value. Each pre-position function has two settings: Setpoint and Mode. The setting range of
each pre-position setpoint
A
is identical to that of the corresponding control mode setpoint. The Mode
B
setting determines whether or not the DECS-250 will respond to further setpoint change commands while
the pre-position command is being asserted. If the pre-position mode is Release, setpoint change
commands are accepted to raise and lower the setpoint while the pre-position command is being
asserted. Additionally, if the inactive pre-position mode is Release and internal tracking is enabled, the
pre-position value will respond to the tracking function. If the pre-position mode is Maintain, further
setpoint change commands are ignored while the appropriate contact input is closed. Additionally, if the
inactive pre-position mode is Maintain and internal tracking is enabled, the inactive mode will maintain the
inactive setpoint at the pre-position value and override the tracking function. A portion of the pre-position
setpoints for var and PF modes are illustrated in Figure 17. (Pre-Position Setpoints for AVR, FCR, and
FVR modes are similar and not shown here.)
Содержание DECS-250
Страница 2: ......
Страница 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Страница 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Страница 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Страница 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Страница 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Страница 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Страница 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Страница 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Страница 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Страница 108: ...92 9440300990 Rev J Power System Stabilizer DECS 250 Figure 85 PSS Function Blocks and Software Switches ...
Страница 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Страница 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Страница 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Страница 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Страница 128: ...112 9440300990 Rev J Mounting DECS 250 Figure 105 Panel Cutting and Drilling Dimensions for DECS 250 Panel Mounting ...
Страница 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Страница 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Страница 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Страница 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Страница 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Страница 341: ...9440300990 Rev J 325 DECS 250 Contact Expansion Module Figure 188 CEM 2020 Input Contact and Output Contact Terminals ...
Страница 351: ......