step-down transformers in the system. The DECS-250 adjusts the sensed generator voltage by this
percentage. This setting also appears on the Voltage Matching screen, below. When the value is
changed, it is reflected in both places.
Angle Compensation
An angle compensation
K
setting is provided to offset phase shift caused by transformers in the system.
The angle compensation value is added only to the bus angle. For example, it is given that the generator
and bus are synchronized but the DECS-250 metered slip angle reads –30°. Equation 1, below, illustrates
the DECS-250 slip angle calculation. This means that the generator angle is lagging behind the bus angle
by 30° due to transformer phase shift. To compensate for this phase shift, the angle compensation setting
should contain a value of 330°. This value is added to the metered bus angle resulting in an adjusted slip
angle of zero degrees. Only the metered bus angle is affected by the angle compensation setting, the
metered generator angle is not biased by the DECS-250.
𝐺𝐺 −
(
𝐵𝐵
+
𝐴𝐴
) =
𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆
𝐴𝐴𝐴𝐴𝐴𝐴𝑆𝑆𝐴𝐴
Equation 1. DECS-250 Metered Slip Angle
Where:
G = metered generator angle
B = metered bus angle
A = angle compensation value
Failure of Synchronization
Generator synchronization is aborted if generator synchronization fails to occur within a timeframe
L
established by the user.
BESTCOMS
Plus
®
generator synchronization settings are illustrated in Figure
10.
Figure 10. Generator Synchronizer Settings
A
Sync Type
: Select Anticipatory or Phase Lock Loop.
B
Slip Frequency
: Adjustable from 0.1 to 0.5 Hz in 0.05 Hz increments.
C
Min Slip Control Limit:
Adjustable from 0.1 to 2.0 Hz in 0.1 Hz increments.
D
Max Slip Control Limit:
Adjustable from 0.1 to 2.0 Hz in 0.1 Hz increments.
E
Fgen>Fbus
: Select Enable or Disable.
F
Breaker Closing Angle
: Adjustable from 3 to 20
°
in 0.5
°
increments.
G
Sync Activation Delay
: Adjustable from 0.1 to 0.8 s in 0.1 s increments.
H
Voltage Window
: Adjustable from 2 to 15% in 0.5% increments.
I
Vgen>Vbus
: Select Enable or Disable.
Содержание DECS-250
Страница 2: ......
Страница 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Страница 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Страница 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Страница 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Страница 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Страница 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Страница 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Страница 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Страница 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Страница 108: ...92 9440300990 Rev J Power System Stabilizer DECS 250 Figure 85 PSS Function Blocks and Software Switches ...
Страница 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Страница 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Страница 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Страница 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Страница 128: ...112 9440300990 Rev J Mounting DECS 250 Figure 105 Panel Cutting and Drilling Dimensions for DECS 250 Panel Mounting ...
Страница 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Страница 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Страница 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Страница 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Страница 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Страница 341: ...9440300990 Rev J 325 DECS 250 Contact Expansion Module Figure 188 CEM 2020 Input Contact and Output Contact Terminals ...
Страница 351: ......