9440300990 Rev J
9
DECS-250
Power Inputs
Power Inputs
Power is applied to two separate inputs: control power and operating power. The control power input
supplies power to an internal power supply that provides power for logic, protection, and control functions.
The power stage uses the operating power input as the source for the converted excitation power that it
applies to the field.
Control Power
Two inputs supply the DECS-250 with control power. One input accepts dc control power and the other
input accepts ac control power. The level of acceptable control power voltage is determined by the style
number. One of two levels is possible. Style Lxxxxxx indicates a nominal voltage of 24 or 48 Vdc and
accepts a voltage range of 16 to 60 Vdc. Style Cxxxxxx indicates a nominal voltage of 125 Vac/Vdc and
accepts a voltage range of 90 to 150 Vdc and 82 to 132 Vac (50/60 Hz). One input (either dc or ac) is
sufficient for operation but two inputs provide redundancy (for style Cxxxxxx only). When both control
power inputs are used, an isolation transformer is required for the ac input. DC control power is applied at
terminals BATT+ and BATT–. AC control power is applied at terminals L and N.
Operating Power
Caution
For redundant applications with a single-phase, 300 Hz Marathon
PMG, only one DECS-250 can be connected to the PMG at a time. In
redundant applications, a contactor should be used for each DECS-
250 power input or equipment damage may result.
If using 277 Vac operating power input, the connection must be
configured as L-N single-phase or equipment damage may result.
Operating power is applied at terminals A, B, and C. To achieve the desired level of excitation, the
appropriate operating power input voltage must be applied. Table 2 lists the acceptable operating power
voltage ranges for the DECS-250. The operating power frequency range for the DECS-250 is 50 to 500
hertz for all voltages.
Table 2. DECS-250 Operating Power Specifications
Desired Nominal
Excitation Power Voltage
Applied Operating
Power Voltage Range
32 Vdc
56 to 70 Vac
63 Vdc
100 to 139 Vac, or 125 Vdc
125 Vdc
190 to 277 Vac, or 250 Vdc
Inrush Current Reduction Module (ICRM)
During DECS-250 power-up, the optional ICRM prevents damage to the DECS-250 by limiting inrush
current to a safe level. When operating power is applied to the DECS-250, the ICRM limits the inrush
current by adding a high level of resistance between the DECS-250 and the power source. Once the
inrush current subsides, the series resistance diminishes quickly to allow nominal, steady-state current
flow.
Содержание DECS-250
Страница 2: ......
Страница 6: ...iv 9440300990 Rev J Revision History DECS 250 ...
Страница 16: ...xiv 9440300990 Rev J Contents DECS 250 ...
Страница 20: ...4 9440300990 Rev J Introduction DECS 250 ...
Страница 28: ...12 9440300990 Rev J Power Stage DECS 250 ...
Страница 32: ...16 9440300990 Rev J Voltage and Current Sensing DECS 250 ...
Страница 40: ...24 9440300990 Rev J Synchronizer DECS 250 ...
Страница 52: ...36 9440300990 Rev J Auxiliary Control DECS 250 ...
Страница 56: ...40 9440300990 Rev J Contact Inputs and Outputs DECS 250 ...
Страница 84: ...68 9440300990 Rev J Limiters DECS 250 ...
Страница 108: ...92 9440300990 Rev J Power System Stabilizer DECS 250 Figure 85 PSS Function Blocks and Software Switches ...
Страница 114: ...98 9440300990 Rev J Power System Stabilizer DECS 250 Figure 96 PSS Parameter Settings ...
Страница 124: ...108 9440300990 Rev J Stability Tuning DECS 250 ...
Страница 126: ...110 9440300990 Rev J Mounting DECS 250 Figure 103 Overall and Projection Mounting Dimensions ...
Страница 127: ...9440300990 Rev J 111 DECS 250 Mounting Figure 104 DECS 250 Escutcheon Plate Dimensions ...
Страница 128: ...112 9440300990 Rev J Mounting DECS 250 Figure 105 Panel Cutting and Drilling Dimensions for DECS 250 Panel Mounting ...
Страница 198: ...182 9440300990 Rev J Timekeeping DECS 250 ...
Страница 210: ...194 9440300990 Rev J CAN Communication DECS 250 ...
Страница 304: ...288 9440300990 Rev J Maintenance DECS 250 ...
Страница 316: ...300 9440300990 Rev J Specifications DECS 250 ...
Страница 334: ...318 9440300990 Rev J Analog Expansion Module DECS 250 ...
Страница 341: ...9440300990 Rev J 325 DECS 250 Contact Expansion Module Figure 188 CEM 2020 Input Contact and Output Contact Terminals ...
Страница 351: ......