Maintenance and care
Ex p Control Unit
SIEMENS Set
Page 64 of 80
01-37A2-7D0004_SIEMENS_Manual_Exp-Control-Unit_20220216_0_en.docx
Rev. 0
Disclaimer: We reserve the right to make technical changes. Changes, errors and printing errors do not justify claims for damages.
10
Maintenance and care
Find out about the general safety instructions before starting
work (see Chapter 2.4 Safety instructions).
Carry out maintenance and care in accordance with the following sections,
unless otherwise agreed for customer-specific versions.
Types of purge gas
Only inert gas (e.g. nitrogen) or purified and dry instrument air is permitted as
purge gas. In any case, a filter must be installed upstream if the quality with
regard to foreign particles is not guaranteed. The following quality
characteristics of the purge gas should be met:
Residual dust: < 40 µm
Residual water: dew point +3 °C
Residual oil content: 1 mg/m³
Maintenance work
Maintenance intervals
MAINTENANCE INTERVALS
Maintenance according to the following maintenance schedule is
recommended in the case of proper operation, observing the
installation instructions and ambient conditions.
ATTENTION
MAINTENANCE AND CARE
The currently applicable regulations and the national provisions must
be observed for maintenance, service and inspection of the
equipment!
Operation and maintenance work may be performed by trained
specialist personnel only. The statutory regulations and the other
binding directives on occupational health and safety, accident
prevention and environmental protection must be observed.
When opening covers or removing parts, unless possible by hand, live
parts may be exposed. Connecting parts may also be live.
Maintenance interval
Work to be performed
Monthly
Visual inspection according to Chapter 10.2.2
Semi-annually
Cleaning according to Chapter 10.2.3
Annually
Regular maintenance according to Chapter 10.2.4