Commissioning
Ex p Control Unit
SIEMENS Set
Page 58 of 80
01-37A2-7D0004_SIEMENS_Manual_Exp-Control-Unit_20220216_0_en.docx
Rev. 0
Disclaimer: We reserve the right to make technical changes. Changes, errors and printing errors do not justify claims for damages.
Procedure
Connect computer with Ex p control unit
Activate programming switch
Log in to the WEB interface with the user level
Selected Extended / Sensors menu
Activate the required temperature sensor, e.g. temperature sensor 1, by
clicking PT100 or 1000
Manual button changes to
Confirm pop-up window with altered value
Activate display unit in °C or °F by clicking on the button. Display changes
to
Confirm pop-up window with altered value
Select T sensors / temperature sensor 1 menu
Signaling for active sensor is displayed by way of the green indicator
Store switching value 1
e.g. 25 °C
Confirm pop-up window with altered value
Store switching value 2
e.g. 35 °C
Confirm pop-up window with altered value
Store switching value 3
e.g. 60 °C
Confirm pop-up window with altered value
Store switching hysteresis
e.g. 5 K
Functions are activated or deactivated with a hysteresis of
5K
Select function for switching value 1
e.g. open valve 1
Function “cooling via purge air “
Confirm pop-up window with altered value
Select function for switching value 2
e.g. warning message plain text
Function “warning message is
read out as plain text message”
Confirm pop-up window with altered value
Select function for switching value 3
e.g. deactivation Ex p (K1) and alarm message plain text
Function “Taking back of the enable of the Ex p equipment and issue of an
alarm message as plain text“
Confirm pop-up window with altered value