Ex p Control Unit
SIEMENS Set
Maintenance and care
Rev. 0
01-37A2-7D0004_SIEMENS_Manual_Exp-Control-Unit_20220216_0_en.docx
Page 69 of 80
Disclaimer: We reserve the right to make technical changes. Changes, errors and printing errors do not justify claims for damages.
10.4.2.2
Warning messages
Status
Code
Plain text
00000005
Bypass active
The bypass is activated on the control unit.
00000006
Door contact / main switch open
The main switch or bridge HS_IN / HS_OUT is not closed.
00000007
p2 not reached
The setpoint value p2 “pre-alarm” is not reached.
00000008
p4 exceeded
The setpoint value p4 “Maximum pressure – operation” is exceeded.
00000009
p5 exceeded
The setpoint value p5 “Maximum pressure – Purge” is exceeded.
0000000A
Temperature sensor 1 exceeded
Temperature sensor 1 exceeded
0000000B
Temperature sensor 2 exceeded
The setpoint temperature value at sensor 2 is exceeded.
0000000C
Temperature sensor 3 exceeded
The setpoint temperature value at sensor 3 is exceeded.
10.4.2.3
Alarm messages
Status
Code
Plain text
0000000D
Ex p inactive
The protected device is deactivated.
0000000E
Device fault 1
HW test error in safety processors with the exception of the barriers and sensor
errors. The message is generated for the service processor if an error occurs in the
HW status.
0000000F
Device fault 2
Status of the barriers without sensor board feedback
00000010
Device fault 3
There is an error in the area of the internal temperature monitoring / sensors.
00000011
Device fault 4
The system status for safety processors equals "serious error"
00000012
Sensor error 1
Pressure sensor error or sensor board status error
00000013
Sensor error 2
Power sensor error.
Error is only shown if the sensors are active.