Electrical connections
Ex p Control Unit
SIEMENS Set
Page 38 of 80
01-37A2-7D0004_SIEMENS_Manual_Exp-Control-Unit_20220216_0_en.docx
Rev. 0
Disclaimer: We reserve the right to make technical changes. Changes, errors and printing errors do not justify claims for damages.
6.2.1.4
Terminal row “X12“
Floating signaling K2 can be classified as pure enable according
to SIL when used.
A floating signal (4x NO) is available on
the Ex p control unit. This signal can
either be used as an enable that is also
safety related. Or it can be used as a
floating signal.
Terminal
Connection
Function
1
K2_1 - NO
Normally open contact
2
K2_2 – NO
Normally open contact
3
K2_3 – NO
Normally open contact
4
K2_4 – NO
Normally open contact
5
K2_1´ - NO
Normally open contact
6
K2_2´ - NO
Normally open contact
7
K2_3´ - NO
Normally open contact
8
K2_4´ - NO
Normally open contact
6.2.1.5
Terminal row “X7“
ATTENTION
MATERIAL DAMAGE DUE TO INCORRECT PRE-FUSING.
Valve or Ex p control unit may be damaged.
Operate the digital outlet valve only with a 1.0 A pre-fuse and the
proportional outlet valve only with a 1.6 A pre-fuse.
The terminal row X7 is used to connect the purge gas valve and the
accompanying valve fuse. Furthermore, the terminal points 6 – 9 are intended for
unused wires of the LAN connection cable.
Terminal
Connection
Function
1
Pre-fuse
Connection pre-fuse valve
2
Pre-fuse
Connection pre-fuse valve
3
Valve +
+ conductor valve
4
Valve -
GND valve
5
Valve - PE
PE valve
6
L1
BU
For unused LAN cable wire
7
L2
BUWH
For unused LAN cable wire
8
L3
BNWH
For unused LAN cable wire
9
L4
BN
For unused LAN cable wire