Ex p Control Unit
SIEMENS Set
Maintenance and care
Rev. 0
01-37A2-7D0004_SIEMENS_Manual_Exp-Control-Unit_20220216_0_en.docx
Page 67 of 80
Disclaimer: We reserve the right to make technical changes. Changes, errors and printing errors do not justify claims for damages.
Error / Fault
Possible cause
Remedy
“Operate” LED does not
flash during purge time
Setpoint pressure of the
pressure reducer is not
reached
Remove the cap or
eliminate the reduction by
taking suitable measures
Pressure monitor of the
control unit is
inadmissibly closed or has
a reducer
Seal enclosure using
suitable measures
Enclosure leaks during the
pre-purge phase due to
increased internal
pressure
Check purge gas valve for
the presence of supply
voltage
Digital purge gas valve
does not switch to the
small nozzle after the
pre-purge phase
Temperature sensor is
connected, internal
temperature too high
Check purge gas valve for
foreign particles in the
mechanical part
Wait until the increased
flow rate has caused the
internal temperature to
drop or check the set
temperature switching
value
Main switch or bridge to
the terminals Hs_In /
Hs_Out not connected
Switch on main switch or
connect bridge to terminal
Hs_In / Hs_Out
Purge gas valve does not
close
Check purge gas valve for
disconnected supply
voltage
Control unit does not
switch on the electrical
devices after the pre-
purge phase
Pressure in the enclosure
higher than the switching
value ”p4”
Reduce the flow rate of the
air leak needle
Switching value “p4” too
low
Check switching value “p4”
Pressurized enclosure
leaking, switching value
“p1” not reached
Seal pressurized enclosure
The control unit switches
off the electrical devices
after the purge time with
a 5 sec. time delay
Leakage air needle of
digital valve too small
Increase the air flow rate of
the leakage air needle
Switching value “p3“ too
high
Check switching value “p3”
Relays K4 or K5 do not
switch
Wrong selection of
switching parameters
Check switching
parameters