Parameter Descriptions 7-21
MN765
Block Title Parameter (Number)
Selection (Value)
Parameter Name and Description
MISCELLA-
NEOUS
AUTO RESTART
(2301)
Preset Value: 1
Range: 0 - 3
Manual (0)
If set to Manual and a run command (enable signal & FWD or REV command)
is present at power up, the motor will not run. The run command must be
removed then reapplied to start operation. The run command refers to the
enable plus direction (FWD or REV) signals. Restart after Fault - If a fault
occurs during operation, the control must be reset and the run command
must be removed then reapplied to start operation. Note: If Restarts/Hr
(P2302) is zero, the control must be manually reset. If Restarts/Hr (P2302) is
non-zero, the control will automatically attempt to reset the fault but will not
restart until the run command is removed then reapplied to start operation.
At Powerup (1)
If a run command (enable signal & FWD or REV command) is present at
power up, the control will automatically start. Auto restarts enabled at power
up but disabled after a fault.
After Fault (2)
If a fault occurs during operation, the control will automatically reset (after the
restart delay time) to resume operation if the Restarts/Hr (P2302) is set to a
non zero value. Auto restarts disabled at power up but enabled after a fault.
Both (3)
Auto restarts active at power up and after faults. 3 Wire modes, AUTO start
after a fault or loss of power will not occur because the momentary contacts
are open and the run command must again be applied. The run command
refers to the enable plus direction (FWD or REV) lines.
RESTARTS/HOUR
(2302)
Preset Value: 3
Range: 0 - 10
The maximum number of automatic restart attempts before requiring a
manual restart. After one hour without reaching the maximum number of
faults or if power is turned off and on again, the fault count is reset to zero.
RESTART DELAY
(2203)
Preset Value: 3
Range: 0 - 3600 seconds
Sets the time delay after a fault occurs before a fault reset and automatic
restart are attemped. If the fault reset is successful, the restart will occur. If
not successful, a new delay occurs. Useful to allow sufficient time to clear a
fault condition before restart is attempted.
PWM TECHNIQUE
(2304)
Preset Value: 1
Range: 0 - 1
Space Vector (0) Utilizes Vector Orientation to determine pulse firing.
Sine Triangle (1) Utilizes Sine/Triangle Waveform Intersect technique to determine pulse
widths.
Sets the method used to generate the motor voltage PWM signal.
COST OF ENERGY
(2305)
Preset Value: 0.10
Range: 0.00 - 99999.00$/KWH
Sets the billing cost per KWH charged by the local power utility.
RESET ENERGY
(2306)
Preset Value: 0
Range: 0 - 1
No (0) No Action.
Yes (1) Resets the energy counter (in power base of the control).
HOMING SPEED
(2307)
Only available or active in Closed
Vector mode. Ignore for Open
Vector and V/F modes.
Preset Value: 90
Range: 0 - MAX Speed RPM
This parameter sets the speed that the motor shaft will rotate in the forward
direction to “Home” position when the home input switch is closed. Available
only in modes that have a homing (orient) input. For Bipolar and Network
Modes, the speed and ramp rates during this final positioning are set by
Preset Speed 1 and ACC/DEC Group 2 respectively.
Table 7-2 Level 2 Parameter Block Definitions Continued
Содержание VS1GV21-1B
Страница 1: ...10 11 Installation Operating Manual MN765 VS1GV AC Closed Vector Control...
Страница 12: ...2 2 General Information MN765...
Страница 16: ...3 4 Installing the Drive MN765...
Страница 78: ...6 16 Using the Keypad MN765...
Страница 132: ...9 14 Troubleshooting MN765...
Страница 169: ...Technical Specifications A 13 MN765 OM2000A11 Size B NEMA 4X Figure A 2 Drive Dimensions and Weights Continued...
Страница 172: ...A 16 Technical Specifications MN765...
Страница 200: ...E 2 Remote Keypad Mounting Template MN765...
Страница 201: ...Remote Keypad Mounting Template E 3 MN765...
Страница 202: ...E 4 Remote Keypad Mounting Template MN765...