7-2 Parameter Descriptions
MN765
Block Title Parameter (Number)
Selection (Value)
Parameter Name and Description
RAMP
RATES
(Continued)
PL DEC TIME
(1113)
Preset Value: 1.0
Range: 0.0 to 3600.0 Seconds
Time to stop the motor from maximum drive speed during a power loss.
% Maximum Speed
100
80
60
40
20
-20
-40
0
Accel Time
Start
S-Accel 1
End
S-Accel 1
Decel Time
Start
S-Decel 1
End
S-Decel 1
Speed Curve
(Accel)
Speed Curve
(Decel)
Seconds
2
4
6
8
10
Commanded Speed
12
Decel Rate
Accel Rate
JOG
SETTINGS
JOG SPEED
(1201)
Preset Value: 210
Range: 0 - MAX Speed RPM
Jog Speed is the programmed speed used during jog. Jog can be initiated from the
keypad or terminal strip. At the Keypad, press the JOG key then press and hold the
direction (FWD or REV). For Standard Run 3Wire mode, close the JOG input (J2-12)
at the terminal strip then close and maintain the direction input (J2-9 or J2-10).
Process Control mode operation is different. If the terminal strip Process Control
Enable input (J2-13) is closed, pressing the Keypad JOG key (or closing J2-14) will
cause the drive to move in the direction of the error (without pressing FWD or REV).
JOG ACCEL TIME
(1202)
Preset Value: 10.0
Range: 0.0 to 3600.0 Seconds
The accel rate or time to reach max Speed.
Time to reach Jog Speed=(Jog Speed/Max Speed) x (Jog Accel Time).
JOG START S-ACC
(1203)
Preset Value: 0.0
Range: 0.0 to 100.0%
Start S-Curve Acceleration as a percentage of jog accel time.
JOG END S-ACC
(1204)
Preset Value: 0.0
Range: 0.0 to 100.0%
End S-Curve Acceleration as a percentage of jog accel time.
JOG DECEL TIME
(1205)
Preset Value: 10.0
Range: 0.0 to 3600.0 Seconds
The decel rate or time to decel from max Speed.
Time to reach zero speed=(Jog Speed/Max Speed) x (Jog Decel Time).
JOG START S-DEC
(1206)
Preset Value: 0.0
Range: 0.0 to 100.0%
Start S-Curve Deceleration as a percentage of jog decel time.
JOG END S-DEC
(1207)
Preset Value: 0.0
Range: 0.0 to 100.0%
End S-Curve Deceleration as a percentage of jog decel time.
JOG FORWARD
(1209)
Preset Value: 1
Range: 0 - 1
Off (0) Mode Disabled.
On (1) Enables Jog in the drive forward direction at Jog speed for keypad mode.
JOG REVERSE
(1210)
Preset Value: 1
Range: 0 - 1
Off (0) Mode Disabled.
On (1) Enables Jog in the drive reverse direction at Jog speed for keypad mode.
Table 7-1 Level 1 Parameter Block Definitions Continued
Содержание VS1GV21-1B
Страница 1: ...10 11 Installation Operating Manual MN765 VS1GV AC Closed Vector Control...
Страница 12: ...2 2 General Information MN765...
Страница 16: ...3 4 Installing the Drive MN765...
Страница 78: ...6 16 Using the Keypad MN765...
Страница 132: ...9 14 Troubleshooting MN765...
Страница 169: ...Technical Specifications A 13 MN765 OM2000A11 Size B NEMA 4X Figure A 2 Drive Dimensions and Weights Continued...
Страница 172: ...A 16 Technical Specifications MN765...
Страница 200: ...E 2 Remote Keypad Mounting Template MN765...
Страница 201: ...Remote Keypad Mounting Template E 3 MN765...
Страница 202: ...E 4 Remote Keypad Mounting Template MN765...