PLC Mode Description 10-5
MN765
Table 10-2 PLC Logical Operators
ID
Description
0
OR - Performs logical OR operation on input conditions
1
AND - Performs logical AND operation on input conditions
2
XOR - Performs logical XOR operation on input conditions
3
NOR - Performs logical NOR operation on input conditions
4
NAND - Performs logical NAND operation on input conditions
Table 10-3 PLC Actions
ID
Description
0
Digital Output 1 - If the input condition is True then Digital Output 1 (J2-17,18) will be active otherwise it is inactive
NOTE: Digital output 1 must have been set to “PLC” using P1501
1
Digital Output 2 - If the input condition is True then Digital Output 2 (J2-19,20) will be active otherwise it is inactive
NOTE: Digital output 2 must have been set to “PLC” using P1502
2
Relay Output 1 - If the input condition is True then Relay Output 1 (J3-25,26,27) will be active otherwise it is inactive
NOTE: Relay output 1 must have been set to “PLC” using P1503
3
Reserved (Workbench - Fault)
4
Drive Enable/Disable - If the condition is True then the drive is capable of producing power. If the condition is False
the drive is disabled. NOTE: If not programmed, J2-8 alone enables the drive NOTE: The drive's hardware enable
input (J2-8) must be is active for this action.
5
Jog Reverse - If the condition is True then the motor will jog in the reverse direction at the speed set by P1201 if
jogging is enabled. NOTE: If both jog forward and reverse are active the motor stops
6
Jog Forward - If the condition is True then the motor will jog in the forward direction at the speed set by P1201 if
jogging is enabled. NOTE: If both jog forward and reverse are active the motor stops
7
Reserved (Workbench - Hold)
8
Stop Enable/Disable - If the input condition is True the motor is stopped.
9
Reserved (Workbench - Error Deceleration)
10
Reserved (Workbench - Cancel)
11
Reserved (Workbench - Disable)
12
Reserved (Workbench - Forced Abort)
13
Reserved (Workbench - Fast Gear)
18
Jog Enable - Allows jogging if True else jogging is disabled
19
Fault - If the input condition is True a “PLC Fault” is triggered. If using J2-16 to generate a PLC Fault Condition,
P2201 must be set to “OFF” to avoid a conflict with external trip.
20
Forward Enable/Disable - If the input condition is True forward motion is enabled otherwise it is disabled.
21
Reverse Enable/Disable - If the input condition is True reverse motion is enabled otherwise it is disabled.
22
Acc/Dec Group Select - If the input condition is True then Acc/Dec group 2 is selected otherwise group 1 is selected.
NOTE: If this action is not programmed Group 1 is active by default.
23
Reset - If the input condition is True a reset request is issued. NOTE: This action is edge triggered on a False to True
transition. NOTE: Pre-existing faults/alarms may or may not be cleared.
24
Preset Speed/Analog - If the input condition is True then the Preset Speed Select Table Index sets the speed reference
from the Preset Speeds (P1001-P1015) else the Command Source (P1402) selects the speed reference. NOTE: If this
action is not programmed P1402 is always active. NOTE: If the Preset Speed Select Table Index is not programmed
then P1001 is used.
25
Preset Speed Select Table Index Bit 0 - If the input condition is True then bit 0 of the Preset Speed Select Table Index
is set else it is reset. NOTE: If this action is not programmed then bit 0 is reset.
26
Preset Speed Select Table Index Bit 1 - If the input condition is True then bit 1 of the Preset Speed Select Table Index
is set else it is reset. NOTE: If this action is not programmed then bit 1 is reset.
27
Preset Speed Select Table Index Bit 2 - If the input condition is True then bit 2 of the Preset Speed Select Table Index
is set else it is reset. NOTE: If this action is not programmed then bit 2 is reset.
Содержание VS1GV21-1B
Страница 1: ...10 11 Installation Operating Manual MN765 VS1GV AC Closed Vector Control...
Страница 12: ...2 2 General Information MN765...
Страница 16: ...3 4 Installing the Drive MN765...
Страница 78: ...6 16 Using the Keypad MN765...
Страница 132: ...9 14 Troubleshooting MN765...
Страница 169: ...Technical Specifications A 13 MN765 OM2000A11 Size B NEMA 4X Figure A 2 Drive Dimensions and Weights Continued...
Страница 172: ...A 16 Technical Specifications MN765...
Страница 200: ...E 2 Remote Keypad Mounting Template MN765...
Страница 201: ...Remote Keypad Mounting Template E 3 MN765...
Страница 202: ...E 4 Remote Keypad Mounting Template MN765...