Power Wiring 4-9
MN765
Figure 4-6 Size B and C Single Phase Power Connections to a 3-Phase Control
L1
L2
L1
L2
L3
Earth
*Optional components not provided with control.
Note 3
Baldor
Control
*Optional
Line
Reactor
Note 1
Note 3
A1
B1
A2
B2
Note 4
GND
Note 2
*Fuses
Single Phase 2 Wire Connections
Single Phase 3 Wire Connections
L1
*Optional
Line
Reactor
A1
A2
*Fuse
Neutral
L1
L2
L3
Earth
Baldor
Control
GND
Notes:
1.
See Protective Devices described previously in this section.
2.
Use same gauge wire for Earth ground as is used for L1 and L2.
3.
Metal conduit should be used. Connect conduits so the use of a
Reactor or RC Device does not interrupt EMI/RFI shielding.
4.
See Line/Load Reactors described previously in this section.
Line Reactors are built-in for size B and larger controls.
IMPORTANT:
Do not connect L3.
IMPORTANT:
Do not connect L3.
In order to protect the drive,
Level 2, Drive Configure, Power
Input P2110 should be set to
“Single Phase”.
See recommended tightening torques in Table A-2.
Single Phase Power and Motor Connections VS1GV6XX-XX
Figure 4-7 shows the minimum connections required at the power connector. All cables must be in conduits or shielded
and the conduits or shields must be grounded at the cable entrance. The brake resistor and cable must be in a conduit or
shielded if installed outside the enclosure.
Figure 4-7 Single Phase Control Power Terminals
See recommended tightening torques in Table A-2.
Frame Size AA
GND
TH2
TH1
T3
T2
T1
B-
R2
R1/B+
GND
N
L2
L1
Input AC
Power
Motor Thermal
Leads
*
Motor GND
Motor
Chassis
Ground
*Remove TH1 to TH2 jumper if Motor Thermal Leads are connected.
Dynamic
Brake
Motor
Leads
Note:
An open circuit between TH1 and TH2 will be used by the drive to generate a motor overtemperature fault. Refer to
the fault/troubleshooting information provided in Chapter 9.
1. Access the Power and Motor Terminals (see Cover Removal procedure).
2. Feed the power supply and motor cables into the drive through the cable entrance.
3. Connect the line L1, L2, N and GND to the power terminal connections, Figure 4-7.
4. Connect motor leads to T1, T2, T3 and GND motor terminal connectors.
Содержание VS1GV21-1B
Страница 1: ...10 11 Installation Operating Manual MN765 VS1GV AC Closed Vector Control...
Страница 12: ...2 2 General Information MN765...
Страница 16: ...3 4 Installing the Drive MN765...
Страница 78: ...6 16 Using the Keypad MN765...
Страница 132: ...9 14 Troubleshooting MN765...
Страница 169: ...Technical Specifications A 13 MN765 OM2000A11 Size B NEMA 4X Figure A 2 Drive Dimensions and Weights Continued...
Страница 172: ...A 16 Technical Specifications MN765...
Страница 200: ...E 2 Remote Keypad Mounting Template MN765...
Страница 201: ...Remote Keypad Mounting Template E 3 MN765...