Parameter Descriptions 7-25
MN765
Block Title Parameter (Number)
Selection (Value)
Parameter Name and Description
BRAKE
ADJUST
(Continued)
DC BRAKE TRIGGER
(2505)
Only available or active in V/F
mode. Ignore for Open/Closed
Vector mode.
Preset Value: 0.00
Range: 0.00 - 50.00 Hz
The frequency at which dc injection braking will begin.
BRAKE ON STOP
(2506)
Preset Value: 0
Range: 0 - 1
Off (0) DC Injection Braking not active.
On (1) Enables DC Injection Braking.
DC injection braking will begin when a stop command is issued. After a stop
command, the DC brake voltage will be applied to the motor windings when
the output frequency reaches the DC brake trigger.
BRAKE ON REVERSE
(2507)
Only available or active in V/F
mode. Ignore for Open/Closed
Vector mode.
Preset Value: 0
Range: 0 - 1
Off (0) Brake on Reverse not active.
On (1) DC Injection Braking enabled on a "Change Motor Rotation Direction”
command.
DC Injection braking will begin after a change-motor-rotation command is
issued. After a stop command, the DC brake voltage will be applied to the
motor windings when the output frequency reaches the DC brake trigger.
Braking continues until the motor is stopped or until stop brake time is
exhausted. The motor will then accelerate in the opposite direction.
STOP BRAKE TIME
(2508)
Only available or active in V/F
mode. Ignore for Open/Closed
Vector mode.
Preset Value: 0.0
Range: 0.0 - 60.0 seconds
The maximum number of seconds that DC injection brake voltage will be
applied to the motor windings after a stop command. After the time specified
by this value, DC injection braking is automatically turned off. If DC injection
braking starts at a frequency less than the DC brake trigger parameter, the
stop brake time is calculated as follows:
BrakeTime = StopBrakeTime X (OutputFrequencyatBraking /
DCBrakeTrigger)
BRAKE ON START
(2509)
Only available or active in V/F
mode. Ignore for Open/Closed
Vector mode.
Preset Value: 0
Range: 0 - 1
Off (0) Brake on Start not active.
On (1) Enables Brake on Start.
ON turns DC injection braking ON for a period of time (Start Brake Time)
when a run command is issued. This ensures the motor is not rotating.
Braking will automatically turn off and the motor will accelerate at the end of
the start brake time.
START BRAKE TIME
(2510)
Only available or active in V/F
mode. Ignore for Open/Closed
Vector mode.
Preset Value: 0.0
Range: 0.0 - 60.0 seconds
The amount of time that DC injection braking will be applied after a run
command is issued. This will only occur if brake on start is set to ON. Braking
may cause the motor to overheat for applications that require frequent starts/
stops. Be careful in selecting this value. The start brake time should be just
long enough to ensure the motor shaft is not rotating when a start command
is issued.
Table 7-2 Level 2 Parameter Block Definitions Continued
Содержание VS1GV21-1B
Страница 1: ...10 11 Installation Operating Manual MN765 VS1GV AC Closed Vector Control...
Страница 12: ...2 2 General Information MN765...
Страница 16: ...3 4 Installing the Drive MN765...
Страница 78: ...6 16 Using the Keypad MN765...
Страница 132: ...9 14 Troubleshooting MN765...
Страница 169: ...Technical Specifications A 13 MN765 OM2000A11 Size B NEMA 4X Figure A 2 Drive Dimensions and Weights Continued...
Страница 172: ...A 16 Technical Specifications MN765...
Страница 200: ...E 2 Remote Keypad Mounting Template MN765...
Страница 201: ...Remote Keypad Mounting Template E 3 MN765...
Страница 202: ...E 4 Remote Keypad Mounting Template MN765...