Troubleshooting 9-1
MN765
Chapter 9
Troubleshooting
The VS1GV continuously monitors its status and operation. When a fault occurs, the event and drive status is captured to
help you troubleshoot problems. The following are designed to help in troubleshooting:
• LEDs on the keypad indicate status (Stop, FWD, REV, Jog)
• Fault Codes displayed on the keypad display as they occur
• A log of these faults and the time each occurred is kept in the Event Log
• A trace log for each event stored in the Event log
9.1 Event Log
From the Menu display screen, select Event Log and press enter. If an error is displayed during operation, press the “Help”
key to learn more about the error. If more than one error was logged, access the Event Log and examine each error Entry at
the time of the event to learn more about the error.
Action
Description
Display
Comments
Status Display
After power up the display shows
the Status screen.
STATUS
FWD
LOCAL
DIAG
600r
MAIN
159.5V
600RPM
6.2A
20.00HZ
Press Menu
Displays top level menu options.
STATUS
BASIC PARAMS
ADVANCED PROG
EVENT LOG
DIAGNOSTICS
DIAG
BACK
Press
to move cursor over
the “EVENT LOG” selection.
Press Enter to view the event log.
Event Log Display
LOW INITIAL BUS
0
Date
Time
Entry #
0-9
HH:MM:SS
Displays error name,
Entry # and time the
error occurred.
DD/MM/YY
EV. LOG
STATUS
TRACE
LOW INITIAL BUS
0 4-Jul-06
09:35:00
LOCAL
STOP
Press
to view next entry.
Press F2 to display Trace menu.
Press F1 to return to Status menu.
or
or
Trace
Input states, Output states, various voltage and current values etc. can be viewed to help understand the cause of the fault
condition. Each event in the Event log has its own Fault Trace displays that were captured when that event occurred. Scroll
through the event log to the event you wish to investigate.
Trace Displays
Action
Description
Display
Comments
Event Log Display
Press
to scroll to the
event you want to investigate.
EV. LOG
STATUS
TRACE
LOW INITIAL BUS
3 4-Jul-06
09:42:00
LOCAL
STOP
Press F2 (or press Enter) to show
the fault Trace for the event.
Fault Trace Display
The Fault Latch word is displayed.
0x=Hexadecimal
0b=Binary
STATUS
T0003
BACK
FAULT LATCH
0x0000
EV. LOG
FAULT TRACE
Press
to view next entry.
This is a hex value.
The T0003 indicates the Fault
Trace for event 3 of the event log
is displayed.
or
or
Содержание VS1GV21-1B
Страница 1: ...10 11 Installation Operating Manual MN765 VS1GV AC Closed Vector Control...
Страница 12: ...2 2 General Information MN765...
Страница 16: ...3 4 Installing the Drive MN765...
Страница 78: ...6 16 Using the Keypad MN765...
Страница 132: ...9 14 Troubleshooting MN765...
Страница 169: ...Technical Specifications A 13 MN765 OM2000A11 Size B NEMA 4X Figure A 2 Drive Dimensions and Weights Continued...
Страница 172: ...A 16 Technical Specifications MN765...
Страница 200: ...E 2 Remote Keypad Mounting Template MN765...
Страница 201: ...Remote Keypad Mounting Template E 3 MN765...
Страница 202: ...E 4 Remote Keypad Mounting Template MN765...