
7-1
Chapter 7. Device Operation by Communication
Commands
By sending a write command to a specific data address, the following operations can be executed on this device.
The data address and write data for each operation are as follows.
Device operation
Data address
Decimal
(hexadecimal)
Write data
Decimal (hexadecimal)
Notes
Device status
deletion
9994 (270A)
12345 (3039)*
The device status (alarm, warning, information) is
deleted.
Errors are not deleted.
Automatic zero point
adjustment
9995 (270B)
12345 (3039)*
The current flow rate is reset to 0.
Before executing this command, set to control
mode and SP = 0, or to fully closed mode, and stop
the flow completely.
Total flow volume
reset
9996 (270C)
12345 (3039)*
The total flow volume is reset to 0.
* For Modbus communication, use Function 16 (multiple data write command) to write the data in the above table and “0” in
order.
Ex.: Send message of the communication command for device status deletion (checksum and CRC omitted)
z
For CPL communications
Instruction code
Data address
Write data
STX
0
1
0
0
X
W
S
,
9
9
9
4
W
,
1
2
3
4
5 ETX
*
*
CR LF
*Check code
z
For Modbus communications
Function code Data address
Write data
0
01H
10H
27H 0AH 00H
02H
04H
30H
39H
00H
00H
*
*
*Check code
Содержание F4Q
Страница 10: ......
Страница 14: ......
Страница 46: ......
Страница 66: ...7 2 Chapter 7 Device Operation by Communication Commands...
Страница 68: ......
Страница 70: ......
Страница 71: ...Revision History CP SP 1458E Printed Edn New Page No Description June 2021 1...
Страница 72: ......
Страница 73: ......