6-4
Chapter 6. Communication Data
Item
Data range
/ [unit]
Data address
Decimal
(hexadecimal)
R
W
Notes
Flow rate unit
(communication)
0: mL/min
1: L/min
2: m
3
/h
1005 (03ED)
✓
×
The unit used by the parameter that
reads or writes the instantaneous flow
rate can be read out.
The setting can be changed by C-48,
Flow rate unit (communication).
Totalized flow rate unit
(communication)
0: mL
1: L
2: m
3
1006 (03EE)
✓
×
The unit used by the parameter that
reads or writes the total flow volume
can be read out.
The setting can be changed by
C-50, Totalized flow rate unit
(communication).
z
Example of combining decimal point position and unit:
When the values read for the full scale flow rate, the flow rate digits after the
decimal point (communication), and the flow rate unit (communication) are 5000,
2, and 1 (L/min) respectively, the actual full scale flow rate is as follows.
• Add a decimal point according to the flow rate digits after the decimal point
(communication) setting: 5000
→
50.00
• Add the unit: 50.00
→
50.00 L/min
When writing fixed-point data, use the reverse procedure and write the separated
values.
Data related to operating status
Item
Data range
/ [unit]
Data address
Decimal
(hexadecimal)
R
W
Notes
Alarm status bit for
compatibility with the
MQV
*
1
1201 (04B1)
✓
×
A code indicating the device status is
given for reference.
Use only when replacing an older model
MQV is replaced with the F4Q.
Digital I/O status bit
*
2
1202 (04B2)
✓
×
For an RS command, statuses are
expressed as decimal numbers.
Control condition bit
*
3
1203 (04B3)
✓
×
Operation mode
0: Valve fully closed
1: Valve control
2: Valve fully open
3. Fixed valve MV
1204 (04B4)
✓
If the operation mode is defined by C-16
(Operational mode at error occurrence)
or by C-10, C-11, or C-12 (Digital input
1–3 function assignment), the setting
cannot be changed by communication.
If writing is attempted, a normal
response will be returned.
The operation mode will be “3” (fixed
valve MV) only if “4” (Fixed valve MV)
is set for C-16 (Operational mode at
error occurrence) and an error occurs.
The setting cannot be changed by
communication.
Содержание F4Q
Страница 10: ......
Страница 14: ......
Страница 46: ......
Страница 66: ...7 2 Chapter 7 Device Operation by Communication Commands...
Страница 68: ......
Страница 70: ......
Страница 71: ...Revision History CP SP 1458E Printed Edn New Page No Description June 2021 1...
Страница 72: ......
Страница 73: ......