6-6
Chapter 6. Communication Data
*1. Alarm status bits for compatibility with the MQV (address 1201)
Bit No.
Item
Description
0
Flow rate deviation lower limit event
(AL01)
0: OFF. 1: ON
1
Flow rate deviation upper limit event
(AL02)
0: OFF. 1: ON
2
Undefined (normally 0)
–
3
Undefined (normally 0)
–
4
Sensor error (common to AL81–AL83)
0: OFF. 1: ON
5
Error in the settings set when product
was shipped (AL91, AL92)
0: OFF. 1: ON
6
Undefined (normally 0)
0: OFF. 1: ON
7
User setting error (AL93)
0: OFF. 1: ON
8
Valve overheating prevention limit (AL71) 0: OFF. 1: ON
9 to 15
Undefined (normally 0)
–
*2. Digital I/O status bits (address 1202)
Bit No.
Item
Description
0
Digital output 1 status
0: OFF. 1: ON
1
Digital output 2 status
0: OFF. 1: ON
2
Digital output 3 status
0: OFF. 1: ON
3
Digital input 1 status
0: OFF. 1: ON
4
Digital input 2 status
0: OFF. 1: ON
5
Digital input 3 status
0: OFF. 1: ON
6 to 15
Undefined (normally 0)
–
*3. Control status bits (address 1203)
Bit No.
Item
Description
0
Flow rate (PV control) evaluation
0: Not OK. 1: OK
1
Undefined (normally 0)
–
2
SP analog setting
0: Disabled. 1: Enabled
3
Total flow event
0: OFF. 1: ON
4
SP ramp control
0: Normal operation
1: SP ramp control
5
Undefined (normally 0)
–
6
External 24 V supply
0: None (fallback operation
by USB in progress)
1: In use
7 to 15
Undefined (normally 0)
–
Содержание F4Q
Страница 10: ......
Страница 14: ......
Страница 46: ......
Страница 66: ...7 2 Chapter 7 Device Operation by Communication Commands...
Страница 68: ......
Страница 70: ......
Страница 71: ...Revision History CP SP 1458E Printed Edn New Page No Description June 2021 1...
Страница 72: ......
Страница 73: ......