3-1
Chapter 3. Settings
3 - 1
Communication Function Settings
Specify the following to use the communication function of this device.
Display
Parameter name
Settings and description
Initial value
Notes
C-30
Communication address setting
0: Communication function
disabled
1 to 127
0
C-31
Transfer speed selection
0: 38400 bps
1: 19200 bps
2: 9600 bps
3: 4800 bps
1
C-32
Data format selection
0: Even parity, 1 stop bit
1: No parity, 2 stop bits
0
Data bits: 8
C-33
Communication protocol
0: Modbus-RTU
1: CPL
1
C-47
Totalized flow rate
communication data format
0: First 4 last 4 digits
1: Upper 16 bits + lower 16
bits
0
Total flow–related
data is read/written by
combining/separating
the upper and lower
values.
C-48
Flow rate unit (communication)
0: mL/min
1: L/min
2: m
3
/h
-
Specifies the unit and
the number of decimal
places of fixed-point
data.
The initial value differs
according to the
model.
The unit and the
number of decimal
places set here do
not apply to the data
displayed on the panel.
C-49
Flow rate digits after the decimal
point (communication)
0 to 3
-
C-50
Totalized flow rate unit
(communication)
0: mL
1: L
2: m
3
-
C-51
Totalized flow rate digits after the
decimal point (communication)
0 to 3
-
Содержание F4Q
Страница 10: ......
Страница 14: ......
Страница 46: ......
Страница 66: ...7 2 Chapter 7 Device Operation by Communication Commands...
Страница 68: ......
Страница 70: ......
Страница 71: ...Revision History CP SP 1458E Printed Edn New Page No Description June 2021 1...
Страница 72: ......
Страница 73: ......