6-16
Chapter 6. Communication Data
Data related to parameter settings
Item
Data range
/ [unit]
Data address
Decimal
(hexadecimal)
R
W
Notes
(P-1)
Flow rate OK judgment
range
(0.5 to 100 % FS)*
2
2201 (0899)
✓
✓
The value is without a decimal
point.*
1
(P-2)
Flow rate OK judgment
hysteresis
(0.5 to 100 % FS)*
2
2202 (089A)
✓
✓
(P-3)
Flow rate deviation
upper limit event
(0.5 to 100 % FS)*
2
2203 (089B)
✓
✓
(P-4)
Flow rate deviation
upper limit event
hysteresis
(0.5 to 100 % FS)*
2
2204 (089C)
✓
✓
(P-5)
Flow rate deviation
lower limit event
(0.5 to 100 % FS)*
2
2205 (089D)
✓
✓
(P-6)
Flow rate deviation
lower limit event
hysteresis
(0.5 to 100 % FS)*
2
2206 (089E)
✓
✓
(P-7)
Flow rate deviation
event judgment delay
time
5 to 9999 [× 0.1 s]
2207 (089F)
✓
✓
(P-8)
Digital output 1 delay
time
0 to 9999 [× 0.1 s]
2208 (08A0)
✓
✓
(P-9)
Digital output 2 delay
time
0 to 9999 [× 0.1 s]
2209 (08A1)
✓
✓
(P-10)
User-set gas conversion
factor (C.F.)
40 to 9999 [× 0.001]
2210 (08A2)
✓
✓
Before using this setting, please
contact us.
Some gas types may not be
supported.
(P-11)
Undefined
Always 0
2211 (08A3)
–
–
Returns “0” when the setting is read
and returns a normal response when
written.
(P-12)
Undefined
Always 0
2212 (08A4)
–
–
(P-13)
Undefined
Always 0
2213 (08A5)
–
–
(P-14)
Undefined
Always 0
2214 (08A6)
–
–
Содержание F4Q