6-7
Chapter 6. Communication Data
*4. Device status bits (addresses 1209 to 1212)
These bits are used for errors, alarms, warnings, and information.
Bit No.
Item
Description
0
Zero point adjustment diagnosis
0: OFF. 1: ON
1
SP is being limited
0: OFF. 1: ON
2
Valve overheat prevention limit
0: OFF. 1: ON
3
Flow rate warning
0: OFF. 1: ON
4
Undefined (normally 0)
–
5
User-defined settings error
0: OFF. 1: ON
6
Communication protocol error
0: OFF. 1: ON
7
Flow rate control error
0: OFF. 1: ON
8
Watchdog time-out
0: OFF. 1: ON
9
Valve error
0: OFF. 1: ON
10
Sensor module error
0: OFF. 1: ON
11
Parameter mismatch
0: OFF. 1: ON
12
Parameter error
0: OFF. 1: ON
13
Hardware error
0: OFF. 1: ON
14
Programmable ROM error
0: OFF. 1: ON
15
Run-time error
0: OFF. 1: ON
Handling Precautions
•
Digital Mass Flow Controller Model F4Q User's Manual
, CP-SP-1461E
(for details of each status)
Data related to the instantaneous flow rate setpoint
Item
Data range
/ [unit]
Data address
Decimal
(hexadecimal)
R
W
Notes
Flow rate setpoint (SP-0)
(0 to 100 % FS)*
2
1401 (0579)
✓
✓
The value is without a decimal
point.*
1
Flow rate setpoint (SP-1)
Same as above
1402 (057A)
✓
✓
Flow rate setpoint (SP-2)
Same as above
1403 (057B)
✓
✓
Flow rate setpoint (SP-3)
Same as above
1404 (057C)
✓
✓
Flow rate setpoint (SP-4)
Same as above
1405 (057D)
✓
✓
Flow rate setpoint (SP-5)
Same as above
1406 (057E)
✓
✓
Flow rate setpoint (SP-6)
Same as above
1407 (057F)
✓
✓
Flow rate setpoint (SP-7)
Same as above
1408 (0580)
✓
✓
*1. For the number of decimal places and the unit of data, see “Flow rate digits after the decimal point” (address 1003) and
“Flow rate unit” (address 1005).
Ex.: If the flow rate digits after the decimal point is set to “1” and the flow rate unit is set to “0” (mL/min), the value “1234”
means 123.4 mL/min.
*2. The setting range is the full scale flow rate (address 1002) multiplied by the percentage in parentheses. (The setting
range varies depending on model and gas type.)
Содержание F4Q
Страница 10: ......
Страница 14: ......
Страница 46: ......
Страница 66: ...7 2 Chapter 7 Device Operation by Communication Commands...
Страница 68: ......
Страница 70: ......
Страница 71: ...Revision History CP SP 1458E Printed Edn New Page No Description June 2021 1...
Страница 72: ......
Страница 73: ......