4-13
Chapter 4. CPL Communication
z
Response message to the WS command
If the data in the data link layer is correct, only a termination code is returned.
4 - 4 Termination Code (p. 4-16)
(for termination code types)
1. Normal response
If data is written correctly, a normal response is returned.
Ex.: A normal response like the one below is returned when all the data is
correctly written.
Termination code (00 = normal)
02H 30H 31H 30H 30H 58H 30H 30H 03H 38H 32H 0DH 0AH
STX 0
1
0
0
X
0
0 ETX 8
2
CR LF
Data link layer
Application layer
Data link layer
2. Error response
If data was not written properly due to an error in the instruction message, an error
response is returned.
Ex.: Error response ("**" stands for the error termination code.)
Termination code (** = an error code)
02H 30H 31H 30H 30H 58H *H *H 03H ??H ??H 0DH 0AH
STX 0
1
0
0
X
*
* ETX ?
?
CR LF
Data link layer
Application layer
Data link layer
Handling Precautions
•
The data address, read count, value to write, and data to read must conform to
the following rules.
•
Use capital letters in character codes for all numbers and characters in the
application layer.
•
Unnecessary zeros or spaces are not allowed.
The underlined portion of “WS,01001W,1” is not allowed.
The underlined portions of “WS,_1001W,01” are not allowed.
Содержание F4Q
Страница 10: ......
Страница 14: ......
Страница 46: ......
Страница 66: ...7 2 Chapter 7 Device Operation by Communication Commands...
Страница 68: ......
Страница 70: ......
Страница 71: ...Revision History CP SP 1458E Printed Edn New Page No Description June 2021 1...
Страница 72: ......
Страница 73: ......