6-17
Chapter 6. Communication Data
Item
Data range
/ [unit]
Data address
Decimal
(hexadecimal)
R
W
Notes
(P-15)
SP ramp control slope 1
0 to 9999
2215 (08A7)
✓
✓
Specifies the change in flow rate per
second.
Note: The unit for the setting varies
depending on the model.
F4Q9200/9500: × 0.1 mL/min
F4Q0002/0005: × 0.001 L/min
F4Q0020/0050: × 0.01 L/min
F4Q0200/0500: × 0.1 L/min
(P-16)
SP ramp control slope 2
0 to 9999
2216 (08A8)
✓
✓
(P-17)
Analog scaling 1
(10 to 100 % FS)*
2
2217 (08A9)
✓
✓
The value is without a decimal
point.*
1
(P-18)
Cumulative flow event
setting (last digits)
0 to 9999 or 0 to 0xFFFF
(see the notes on the
right)
2218 (08AA)
Note: Address
1601 is also
used.
✓
✓
The method for combining
upper and lower digits/bits and
the data range depend on the
setting of C-47, Totalized flow rate
communication data format.*
3
The value is without a decimal
point.*
4
(P-19)
Cumulative flow event
setting (first digits)
Same as above
2219 (08AB)
Note: Address
1602 is also
used.
✓
✓
(P-20)
PV fluctuation control
delay time when fully
closed
0 to 9999 [× 0.1 s]
2220 (08AC)
✓
✓
(P-21)
SP upper limit flow rate
(0 to 100 % FS)*
2
2221 (08AD)
✓
✓
The value is without a decimal
point.*
1
(P-22)
SP lower limit flow rate
(0 to 100 % FS)*
2
2222 (08AE)
✓
✓
(P-23)
Primary pressure
specification
[kPa (gauge)]
2223 (08AF)
✓
✓
(P-24)
Undefined
Always 0
2224 (08B0)
–
–
Returns “0” when the setting is read
and returns a normal response when
written.
(P-25)
Undefined
Always 0
2225 (08B1)
–
–
Returns “0” when the setting is read
and returns a normal response when
written.
(P-26)
Low flow cutoff
threshold
0 to 9999 [× 0.01 %]
2226 (08B2)
✓
✓
(P-27)
Valve manipulated
variable when error
occurs
0 to 100 [%]
2227 (08B3)
✓
✓
This MV applies when “4” (Fixed
valve MV) is set for C-16, Operational
mode at error occurrence.
(P-28)
Digital output 3 delay
time
0 to 9999 [× 0.1 s]
2228 (08B4)
✓
✓
Содержание F4Q
Страница 10: ......
Страница 14: ......
Страница 46: ......
Страница 66: ...7 2 Chapter 7 Device Operation by Communication Commands...
Страница 68: ......
Страница 70: ......
Страница 71: ...Revision History CP SP 1458E Printed Edn New Page No Description June 2021 1...
Страница 72: ......
Страница 73: ......