6-10
Chapter 6. Communication Data
Item
Data range
/ [unit]
Data address
Decimal
(hexadecimal)
R
W
Notes
(C-07)
Digital output 1 type
assignment
0: Not used (OFF at all
times)
1: ON when total flow
event occurs
2: Totalizer pulse
output
3: ON when flow rate
is OK
4: ON when operating
mode = control
5: ON when operating
mode = fully open
6: ON when operating
mode = control or
fully open
7: ON when operating
mode = fully closed
8: ON when error
occurs
9: ON when error or
alarm occur
10: ON when flow rate
deviation event
occurs
−1 to −10: Inverted
output of 1
to 10 above
2007 (07D7)
✓
✓
(C-08)
Digital output 2 type
assignment
2008 (07D8)
✓
✓
(C-09)
Undefined
Always 0
2009 (07D9)
–
–
Returns “0” when the setting is read
and returns a normal response when
written.