6-14
Chapter 6. Communication Data
Item
Data range
/ [unit]
Data address
Decimal
(hexadecimal)
R
W
Notes
(C-35)
SP limit function
0: Disabled
1: Only upper limit
enabled
2: Only lower limit
enabled
3: Upper and lower
limits enabled
2035 (07F3)
✓
✓
(C-36)
Control response setup
0: Response prioritized
1: Standard
2: Stability prioritized
3: PID set by user
2036 (07F4)
✓
✓
(C-37)
Flow rate display unit
change function
0: mL/min
1: L/min
2: m
3
/h
2037 (07F5)
✓
✓
(C-38)
Flow rate digits after
decimal point (display)
0 to 3
2038 (07F6)
✓
✓
(C-39)
Undefined
Always 0
2039 (07F7)
–
–
Returns “0” when the setting is read
and returns a normal response when
written.
(C-40)
Undefined
Always 0
2040 (07F8)
–
–
Returns “0” when the setting is read
and returns a normal response when
written.
(C-41)
Undefined
Always 0
2041 (07F9)
–
–
Returns “0” when the setting is read
and returns a normal response when
written.
(C-42)
Reserved
–
2042 (07FA)
–
–
Returns “0” when the setting is read.
Do not write any values other than
0.
(C-43)
Totalized flow rate unit
(display)
0: mL
1: L
2: m3
2043 (07FB)
✓
✓
(C-44)
Digital output 3 type
assignment
The same as C-07,
Digital output 1 type
assignment
2044 (07FC)
✓
✓
(C-45)
Undefined
Always 0
2045 (07FD)
–
–
Returns “0” when the setting is read
and returns a normal response when
written.
(C-46)
Operation when flow
rate deviation event
occurs
0: No change
1. Fully closed
2: Fully open
2046 (07FE)
✓
✓
(C-47)
Totalized flow rate
communication data
format
0: First 4 last 4
digits
1: Upper 16 bits + lower
16 bits
2047 (07FF)
✓
✓
Data related to total flow volume is
divided into two pieces of data in a
frame when it is sent or received.
With this setting, the combination/
separation method can be specified.
Содержание F4Q
Страница 10: ......
Страница 14: ......
Страница 46: ......
Страница 66: ...7 2 Chapter 7 Device Operation by Communication Commands...
Страница 68: ......
Страница 70: ......
Страница 71: ...Revision History CP SP 1458E Printed Edn New Page No Description June 2021 1...
Страница 72: ......
Страница 73: ......