4-16
Chapter 4. CPL Communication
The following table shows termination codes.
Termination
code
Type
Description
Note
00H
Normal
Normal termination
-
10H
Error
There was an error in the
data address or the number
of data records.
The data cannot be converted to a number, “W” is not set, the
position of the comma is incorrect, etc.
13H
Error
Error in execution
An error occurred during writing or reading.
40H
Error
There was an error in the
number of data records to
access.
The number of data records to be read or written is not from 1
to 10.
43H
Error
Write error
Unsupported write data address, out-of-range data, writing
under read-only conditions, etc.
98H
Error
System error
Memory access failure, etc.
99H
Error
Undefined command
Or other message error
Handling Precautions
•
The success of writing when an error response is returned cannot be
guaranteed. If an error occurs during consecutive data writing, the data may
have been updated halfway. Be sure to write the data again with a correct
message.