6-5
Chapter 6. Communication Data
Item
Data range
/ [unit]
Data address
Decimal
(hexadecimal)
R
W
Notes
Number of the SP
currently in use
0–7
1205 (04B5)
✓
If “3” (SP No. switching) is set for C-10,
C-11, or C-12 (Digital input 1–3 function
assignment), the setting cannot be
changed by communication.
If writing is attempted, an error
response will be returned.
Value of the SP
currently in use
(0–100 % FS)
1206 (04B6)
✓
×
The value is without a decimal point. For
the number of decimal places and the
unit of data, see “Flow rate digits after
the decimal point” (address 1003) and
“Flow rate unit” (address 1005).
PV
(0–100 % FS)
1207 (04B7)
✓
×
Valve manipulated
variable (MV)
0–1000 [× 0.1 %]
1208 (04B8)
✓
×
The value is without a decimal point.
Online SP
1209 (04B9)
✓
✓
This SP is used if “2” (online SP) is set for
C-03, Flow rate setup method (SP setup
method selection).
Error
*
4
1210 (04BA)
✓
×
A code indicating the device status is
given for reference.
For an RS command, statuses are
expressed as decimal numbers.
Alarm
*
4
1211 (04BB)
✓
×
Warning
*
4
1212 (04BC)
✓
×
Information
*
4
1213 (04BD)
✓
×