Operation and Maintenance Manual - GB
G
B
www.atmos.cz
GB-47
• Parameter S44
– is the compressor function for automatic cleaning of the burner by compressed
air, which determines the duration of compressor operation used for preparing a sufficient amount
of compressed air (pressure function S6 = 15) - nonstandard function…
( 2 min )
The set value represents the actual time in minutes.
• Parameter S45
– is the electric valve function for automatic cleaning of the burner by compressed
air, which determines how long the el. valve is open to perfectly clean the combustion chamber of
the burner (S14 = 16) - nonstandard function…
(2 s)
The set value represents the actual time in seconds.
• Parameter S46
– is the burner fan function which sets the type of used fan with rotation scanning.
Number of impulses.…
(12-EBM)
• Parameter S47
– is the function of fan 2 which sets the type of used fan with rotation scanning.
Number of impulses –
do not change the factory setting
…
(0)
a) S47 = 12
- EBM..... radial blower of the burner
b) S47 = 4
- ATAS..... exhaust blower of the boiler
c) S47 = 0
..... second method for switching off the blower 2 speed sensing
• Parameter S48
– characterizes temperature
TEMPERATURE A
in the applications of function
S6 = 17 to 36…
(75 °C)
This is a free function for the reserve output R on the first position (Temperature A = first position
in function S6 = 17 to 36).
• Parameter S49
– characterizes the activation or deactivation difference for
TEMPERATURE A
in the applications of function S6 = 17 to 36…
(5K)
This is the difference for the free function of reserve output R on the first position (difference for
Temperature A = difference for the first position in the function S6 = 17 to 36).
• Parameter S50
– characterizes
TEMPERATURE B
in the applications of function S6 = 25 to
36...….
(75 °C)
This is a free function for the reserve output R on the first position (Temperature b = second posi-
tion in function S6 = 25 to 36).
• Parameter S51
– characterizes the activation or deactivation difference for
TEMPERATURE B
in the applications of function S6 = 25 to 36…
(5K)
This is the difference for the free function of reserve output R on the first position (difference for
Temperature B = difference for the first position in the function S6 = 25 to 36).
• Parameter S52
– characterizes
TEMPERATURE C
in the applications of function S6 = 25 to
36...…
(75 °C)
This is a free function for the reserve output R2 on the first position (Temperature b = second po-
sition in function S14 = 17 to 36).
• Parameter S53
– characterizes the activation or deactivation difference for
TEMPERATURE C
in the applications of function S14 = 17 to 36…
(5K)
This is the difference for the free function of reserve output R2 on the second position (difference
for Temperature C = difference for the second position in the function S14 = 17 to 36).