11. Connection of boilers D30P, D31P, P31 a D45P with an ac-
cumulation tank with solar heating for burner control on the
basis of TS, TK and TV sensors (automatic sensor switching
function), function of controlling the solar pump based on
TSV and TS temperatures
INFO -
The TV, TK and TS sensors on the accumulation tank with solar heating, TSV tem-
perature sensor located in the solar panel, all connected directly to the burner. The AD02
module is inserted under the instrument hood of the boiler and is connected to the terminal
board of the boiler (AD02 module - LA clamp), where it controls the extraction fan of the
boiler (reserve R).
The solar pump is electrically connected directly to the terminal board of the boiler, where
it is controlled directly from the boiler through the R2 reserve.
Required accessories
(not part of the burner): module AD02, three KTF 20 sensors, AGF2 solar
panel sensor up to 400 °C or T7425B1011 up to 300 °C incl. tank - recommended for purchase as the
SC2012 sensor set
System configuration of parameters:
S6 = 4, S14 = 14, S15 = 3
(reserve R – parameter S6 controls the fan, reserve R2 – parameter S14 controls the solar pump)
WARNING
– the AD02 module may be replaced by an AD03 module, whereas only the
required output is used (module AD02 or AD03 – LA clamp)
Pump in the boiler circuit is controlled via the directly installed thermoregulator from the boiler panel.