This method of pump controlling can be used for any ATMOS pellet boiler, and is therefore
recommended.
AD02 or AD03 modules must be inserted and connected under the boiler hood
and the TK sensor must be installed before this function can be activated. After activation, S37,
S38, S39, S40 temperature parameters must be checked and configured.
n)
S14
= 14
….. Reserve function for direct control of solar heating pump from the burner regu-
lation (boiler terminal board). This function control solar pump when automatic sensor switching
function is activated (S15=3), where the boiler is connected with accumulation tank equipped with
solar exchanger and collectors. The system requires TV, TK, TS and solar sensors to be connected
to the TSV solar panel. This function never uses AD02 or AD03 modules.
After activation, S26, S27, S28, S29, S30, S31, S32, S33 temperature parameters must be checked
and configured.
This function is specially designed for boilers: D30P, D31P, P31 a D45P
CAUTION
- the direct controlling function of solar heating from pellet burner cannot be used
for DCxxSP(EP) boilers and boilers with burner built into the upper doors. This function also
cannot be used when the pump is simultaneously controlled in the boiler circuit from the bur-
ner regulation (TK sensor cannot be simultaneously in boiler and accumulation tank)
o)
S14
= 15
….. Reserve function for the compressor control during the function for automatic
burner cleaning using compressed air. Power element designed for switching and powering the
compressor (e.g. contactor) must be connected between reserve output R and the compressor. This
function is connected with S6(14), S41, S42, S43, S44, S45, S46, S47 parameter, which must be
checked and configured.
p)
S14
= 16
….. Reserve function for controlling el.fan during the function for automatic burner
cleaning using compressed air. This function is connected with S6(14), S41, S42, S43, S44, S45,
S46, S47 parameter, which must be checked and configured.
Special function for turning on reserve output R according to the temperature of a concrete
sensor:
a) e.g. function:
TS>……. means that if the TS sensor temperature is higher then the set value in
S48 parameter – Temperature A, reserve output R will be activated
b) e.g. function:
TS<……. means that if the TS sensor temperature is higher then the set value in
S48 parameter – Temperature A, reserve output R will be deactivated
c) e.g. function:
TS,TV>……. means that if the TS and TV sensor temperature is higher at the
same time then the set value in S48 parameter – Temperature A and S50 – Temperature B, reserve
output R will be activated (Temperature A = first position (TS), Temperature B = second position
(Tv)).
d) e.g. function
TS,TK<……. means that if the TS and TK sensor temperature is higher at the
same time then the set value in S48 parameter – Temperature A and S50 – Temperature B, reserve
output R will be deactivated (Temperature A = first position (TS), Temperature B = second posi-
tion (Tk)).