10. Connection of boilers D30P, D31P, P31 a D45P with an ac-
cumulation tank for burner control on the basis of TS and
TV sensors and control of the boiler pump on the basis of
the TK sensor
INFO
– The TV and TS sensors on the accumulation tank and the TK sensor on the boiler
are connected directly to the burner. The AD03 module is inserted under the instrument
hood of the boiler and is connected to the terminal board of the boiler (AD03 module - Lc
clamp – pump, LA clamp - fan), where it controls the extraction fan and pumo in the boiler
circuit.
Required accessories
(not part of the burner): AD03 module and three KTF 20 sensors
System configuration of parameters:
S6 = 4, S14 = 13, S15 = 2
(reserve R – parameter S6 controls the boiler fan, reserve R2 – parameter S14 controls the boiler
pump)