46-GB
Operation and Maintenance Manual - GB
• Parameter S38
– deactivation difference for parameter S37, of the pump in the boiler circuit
(S14 = 13 or S6 = 13)…
(2 K)
If the temperature of the boiler TK drops by more than the deactivation difference S38, the pump
in the boiler circuit will be turned off in the OPERATION or STOP (burn-out) modes.
• Parameter S39
– characterizes the emergency temperature of the boiler TK, during which the
pump in the boiler circuit will be activated (S14 = 13 with modules AD02 or AD03)…
(93 °C)
Activation will be carried out regardless of special functions of the burner (function S40). The
function works based on the deactivation difference specified in parameter S38.
• Parameter S40
– is the function for after-running of the pump in the boiler circuit used based on
boiler type (S14 = 13, S6 = 13)…
(0)
a) S40 = 0
…. The automatic deactivation function for the pump in the the boiler circuit after the
pellet burner burns out is off (after the time specified in parameter T5 runs out). The pump will
be switched off after the temperature of the boiler TK drops (S38, S39). Designated for ceramic
boilers with a large momentum (with the option of stoking with wood).
b) S40 = 1
... The automatic deactivation function for the pump in the boiler circuit after the pellet
burner burns out is on. The pump will be switched off immediately after the burner burns out, after
the time specified in parameter T5 runs out. The function designated by parameter S39 is active. De-
signated for boilers with minimal momentum without ceramics (D14P, P14, D21P, P21, D25P, P25).
• Parameter S41
– is the function for automatic cleaning of the burner by compressed air after a
certain number of work cycles (burn-outs). The function utilizes both reserve outputs (S16 = 15,
S14 = 16) – nonstandard function…
(4)
a) S41 = 1 - 9
… function when the cleaning of the burner will be performed only once after
running a given number of cycles (1, 2, 3, 4, 5, 6, 7, 8, 9 - number of cycles)
b) S41 = 11 - 19
… function when the cleaning of the burner will be performed always twice after
running a given number of cycles (11 = 1, 12 = 2, 13 = 3, 14 = 4, 15 = 5, 16 = 6, 17 = 7, 18 = 8,
19 = 9 - number of cycles) (from 1.4.2013)
If the parameter S41 = 0 or 10, the function is turned off.
• Parameter S42
– is the function for automatic cleaning of the burner by compressed air after a
certain period of operation. On the subsequent termination of a work cycle (burnout), the burner
mouth will be cleaned. The function utilizes both reserve outputs (S16 = 15, S14 = 16) – nonstan-
dard function…
(6 hours)
After the time S42 runs out the pellet burner burns out and cleans. AUTO STOP will be shows on
the burner screen.
The set value represents the actual time in hours.
• Parameter S43
– is the function for automatic cleaning of the burner by compressed air after a cer-
tain period of operation. After the set period elapses, the burner will immediately stop, be cleaned
and re-started if necessary and all conditions for START are met (regardless of parameters S41 and
S42). The function utilizes both reserve outputs (S16 = 15, S14 = 16) – nonstandard function…
(12 hours)
The set value represents the actual time in hours.