Operation and Maintenance Manual - GB
Passwords and their functions
TESTING
– This is a
separate menu
in which you can individually test individual elements of the
burner in case of unclear issues or faults.
CAUTION
– During testing the burner is out of operation and therefore before the start of
testing let the burner properly burn out.
PARAMETERS menu
• Device
–
Product type the electronic unit is designed for…
(A45)
• Parameter Т1
– Time for feeding the ignition amount of pellets…
(60 s)
• Parameter Т2
– Maximum time for ignition of pellets (then a new attempt for ignition
follows)…
(12 min)
• Parameter Т4
– Running time of the worm conveyor after a standstill interval – power control...
(3,4 s)
• Parameter Т5
– Rundown time of the fan after the STOP command - for optimal burning out of
pellets in the combustion chamber…
(15 min)
• Parameter Т6
– Standstill time of the worm conveyor after a running interval - power control...
(16 s.)
• Parameter Т7
– Time to achieve complete burning of the ignition amount of fuel…
(40 s)
• Parameter Т8
– Time of fixed start of the ignition spiral in case of insufficiently burned out
pellets in the combustion chamber after expiration of parameter T5 - only
valid for the first ignition attempt ...
(6 min)
• Parameter Т10
– Time for gradual increase of the power of the burner to the nominal value...
(20 min)
if
T10 = 0,
the function is off
.
Password
Authorization / function
Service engineer
Manufacturer
8118
Switching off and on the fan speed control
Locking and unlocking all parameters
1234
Reset of check algorithms for the ignition spirals