SRV-63 series AC servo drives Detailed parameter description
-141-
6.5.4 Fully-closed loop control
P4.60
1
Frequency division molecular of
external
linear encoder
Setting range
Default
Unit
Available mode
0~2
23
0
-
F
This parameter is used to set the frequency division molecular of external
linear encoder
. When
the setting value is 0, the encoder resolution is the frequency division molecular by default.
P4.60
1
Data size
32bit
Data format
DEC
Modbus address
1920,1921
CANopen address
0x243C,0x00
P4.61
1
Frequency division denominator
of external
linear encoder
Setting range Default
Unit
Available mode
1~2
23
10000
-
F
This parameter is used to set the frequency division denominator of external
linear encoder
,
which corresponds to the
linear encoder
pulse number needed by one-circle rotation of motor.
P4.61
1
Data size
32bit
Data format
DEC
Modbus address
1922,1923
CANopen address
0x243D,0x00
P4.62
1
Direction reversal of external
linear encoder
Setting range Default
Unit
Available mode
0~1
0
-
F
This parameter is used to set the direction reversal of external
linear encoder
feedback counting.
Setting value
Function
[0]
Use the counting value of the
linear encoder
directly
1
Use after the reversing of the counting value of the
linear encoder
P4.62
1
Data size
16bit
Data format
DEC
Modbus address
1924,1925
CANopen address
0x243E,0x00
P4.64
1
Large mixed deviation
setting
Setting range
Default
Unit
Available mode
1~2
27
160000
reference unit
F
In the fully-closed loop control, set the tolerance (mixed deviation) between the user unit
(reference unit) corresponding to the encoder feedback position and user unit (reference unit)
corresponding to the
linear encoder
feedback position. If R0.05 exceeds the setting value, the
drive will report Er22-1.
P4.64
1
Data size
32bit
Data format
DEC
Modbus address
1928,1929
CANopen address
0x2440,0x00
P4.65
1
Mixed deviation clearing
Setting range
Default
Unit
Available mode
0~100
0
Circle
F
This parameter is used to set the condition of mixed control deviation clearing. After rotating for the
set circles, the mixed control deviation will be cleared. If it is set to 0, the deviation will not be
cleared.
P4.65
1
Data size
16bit
Data format
DEC
Modbus address
1930,1931
CANopen address
0x2441,0x00