SRV-63 series AC servo drives Detailed parameter description
-137-
If P4.10 is 1, this parameter can be used to set the external fault command.
Setting value
Function
[0]
Disabled
1
Enabled
P4.22*
Data size
16bit
Data format
DEC
Modbus address
1844,1845
CANopen address
0x2416,0x00
P4.23*
Emergency stop command
Setting range
Default
Unit
Available mode
0~1
0
-
P
S
T
F
If P4.10 is 1, this parameter can be used to set emergency stop command.
Setting value
Function
[0]
Disabled
1
Enabled
P4.23*
Data size
16bit
Data format
DEC
Modbus address
1846,1847
CANopen address
0x2417,0x00
P4.24*
Input command of vibration
control switching
Setting range
Default
Unit
Available mode
0~1
0
-
P
F
If P4.10 is 1, this parameter can be used to set vibration control switching of the drive.
Setting value
Function
[0]
Disabled
1
Enabled
P4.24*
Data size
16bit
Data format
DEC
Modbus address
1848,1849
CANopen address
0x2418,0x00
6.5.3 Extension and application
P4.30
Stop mode
Setting range
Default
Unit
Available mode
0~3
0
-
P
S
T
F
When the servo is turned OFF and when fault alarm occurs, this parameter is used to set whether the
dynamic brake works or not and the state of the servo motor after stop:
P4.30 Setting value
Action
During deceleration
After stopping
[0]
Coast to stop
Keep the inertia operation state
1
Dynamic brake to stop
Keep the inertia operation state
2
Dynamic brake stop
Dynamic braking state
3
External dynamic brake acts Dynamic braking state
Note:
1. When P4.30 is set to 1, the dynamic brake works when motor speed is higher than the value of
P3.58 and does not work otherwise. After motor stops, dynamic brake will stop working.
2. If the running speed of servo motor is faster than rated speed, do not use the dynamic brake. If