SRV-63 series AC servo drives Detailed parameter description
-130-
P3.72
Data size
16bit
Data format
DEC
Modbus address
1744,1745
CANopen address
0x2348,0x00
P3.73
Gain of analog input 3
Setting range
Default
Unit
Available mode
0~2000
300
-
P
S
T
F
This parameter is used to set the gain of analog input 3. The units correspond to different function
of P3.70 are listed below:
P3.70 Setting value
Definition
P3.73 unit
[0]
Invalid
-
1
Speed limit
(r/min)/V
2
Torque limit
0.1%/V
3
Speed command
(r/min)/V
4
Torque command
0.1%/V
5
Speed compensation
(r/min)/V
6
Torque compensation
0.1%/V
7
Negative torque limit
0.1%/V
P3.73
Data size
32bit
Data format
DEC
Modbus address
1746,1747
CANopen address
0x2349,0x00
P3.74
Analog input 3 reverse
Setting range
Default
Unit
Available mode
0~1
0
-
P
S
T
F
This parameter is used to set the voltage polarity of analog input 3.
Setting value
Detection result
[0]
Positive polarity
[+voltage]
→ [positive],[- voltage] → [negative]
1
Negative polarity [+voltage]
→ [negative],[- voltage] → [positive]
P3.74
Data size
16bit
Data format
DEC
Modbus address
1748,1749
CANopen address
0x234A,0x00
P3.75
Voltage protection of
analog input 3
Setting range
Default
Unit
Available mode
0.000~10.000
0.000
V
P
S
T
F
This parameter is used to set the overvoltage protection value of analog input 3.
If the absolute value of analog input 3 voltage exceeds the set value, the system will report alarm.
P3.75
Data size
32bit
Data format
DEC
Modbus address
1750,1751
CANopen address
0x234B,0x00
P3.76
Analog input 3 filter
Setting range
Default
Unit
Available mode
0.0~1000.0
0.0
ms
P
S
T
F
This parameter is used to set the time constant of first order low-pass filter of analog input 3.
P3.76
Data size
16bit
Data format
DEC
Modbus address
1752,1753
CANopen address
0x234C,0x00