SRV-63 series AC servo drives Detailed parameter description
-122-
P3.23
Data size
32bit
Data format
DEC
Modbus address
1646,1647
CANopen address
0x2317,0x00
P3.24
Filter of analog input 2
Setting range
Default
Unit
Available mode
0.0~1000.0
1.0
ms
P
S
T
F
This parameter is used to set the time constant of the first order low-pass filter corresponds to the
command . Setting this parameter can smooth the changing of actual output command when the
command changes violently. Please refer to the figure below:
Command before filtering
AD2
P3.24
P3.24
Time
Command after filtering
Vc
Command after filtering
0.632Vc
0.368Vc
P3.24
Data size
16bit
Data format
DEC
Modbus address
1648,1649
CANopen address
0x2318,0x00
P3.25
Voltage protection of
analog input 2
Setting range
Default
Unit
Available mode
0.000~10.000
0.000
V
P
S
T
F
This parameter is used to set the overvoltage protection value of analog input 2.
Note:
1. The default value 0 means no overvoltage protection;
2. The input voltage should be no more than 10V, otherwise damage may occur to the drive.
P3.25
Data size
32bit
Data format
DEC
Modbus address
1650,1651
CANopen address
0x2319,0x00
P3.26
1
Function selection of
analog input 1
Setting range
Default
Unit
Available mode
0~7
0
-
P
S
T
F
P3.27
1
Function selection of
analog input 2
Setting range
Default
Unit
Available mode
0~7
3
-
P
S
T
F
Select the analog input channel function via this parameter
Setting value
Definition
Unit
[0]
Invalid
-
1
Speed limit
r/min
2
Forward torque limit
0.1%
3
Speed command
r/min
4
Torque command
0.1%
5
Speed compensation
r/min
6
Torque compensation
0.1%
7
Negative torque limit
0.1%