SRV-63 series AC servo drives Detailed parameter description
-131-
P3.77
Deadzone mode of analog
input
Setting range
Default
Unit
Available mode
0~1
0
-
P
S
T
F
Set the deadzone voltage mode of analog input by this parameter
Setting value
Definition
[0]
Normal mode
1
CNC mode. When AI is smaller than the deadzone, the valid value is 0:
When AI is larger than the deadzone, the valid value is AI-deadzone.
P3.77
Data size
16bit
Data format
LIST
Modbus address
1754, 1755
CANopen address
0x234D, 0x00
P3.90
Pulse input filter
Setting range
Default
Unit
Available mode
0~7
2
-
P
S
T
F
This parameter is used to set filter time of the pulse input.
Setting value
Width of pulse input
0
400kHz
1
500kHz
[2]
1MHz
3
2MHz
4
4MHz
5
>4MHz
6
200kHz
7
100kHz
P3.90
Data size
16bit
Data format
DEC
Modbus address
1780,1781
CANopen address
0x235A,0x00
6.5 Extension and application (P4)
6.5.1 Communication setting
P4.01
1
485 local communication
address
Setting range
Default
Unit
Available mode
1~255
1
-
P
S
T
F
This parameter is used to set local (slave) communication address of 485 serial communication.
P4.01
1
Data size
16bit
Data format
DEC
Modbus address
1802,1803
CANopen address
0x2401, 0x00
P4.02
1
CAN communication baud
rate
Setting range
Default
Unit
Available mode
0~5
1
-
P
S
T