SRV-63 series AC servo drives Detailed parameter description
-129-
P3.58
1
Data size
16bit
Data format
DEC
Modbus address
1716,1717
CANopen address
0x233A,0x00
P3.59
Torque reaching range
Setting range
Default
Unit
Available mode
5.0~300.0
50.0
%
T
This parameter is used to set the detection condition for torque reaching output. If the motor
torque feedback exceeds this setting value, the output of TRCH (0x010 of 0x110) is valid. There
is 5% lag in detection.
P3.59
Data size
16bit
Data format
DEC
Modbus address
1718,1719
CANopen address
0x233B,0x00
6.4.4 Analog input 3 adjustment
P3.70
1
Function of analog input
3
Setting range
Default
Unit
Available mode
0~7
4
-
P
S
T
F
This parameter is used to set the function of analog input 3:
Setting value
Definition
Unit
0
Invalid
-
1
Speed limit
(r/min)/V
2
Torque limit *
1
0.1%/V
3
Speed command *
2
(r/min)/V
[4]
Torque command
0.1%/V
5
Speed compensation
(r/min)/V
6
Torque compensation
0.1%/V
7
Negative-direction torque limit
0.1%/V
Note:
*
1
If P3.70 is 2 and P0.09 is 0 or 4, the analog input 3 corresponds to the positive torque limit
internally and P0.62~P0.65, P3.23~P3.25 correspond to the negative torque limit internally.
*
2
If P3.70 is 3, P0.42~P0.45, P3.20~P3.22 are invalid.
P3.70
1
Data size
16bit
Data format
DEC
Modbus address
1740,1741
CANopen address
0x2346,0x00
P3.71
Zero offset of analog
input 3
Setting range
Default
Unit
Available mode
-10.000~10.000
0.000
V
P
S
T
F
The zero offset voltage of analog input 3.
P3.71
Data size
32bit
Data format
DEC
Modbus address
1742,1743
CANopen address
0x2347,0x00
P3.72
Dead zone of analog
input 3
Setting range
Default
Unit
Available mode
0.000~3.000
0.000
V
P
S
T
F
Dead zone range of analog input 3.